Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE20-02240
StatusFinaled
Name DAKOTA ELECTRIC INC
Site Address 1483 E SHENANDOAH DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Install 15 anp 240 volt circuit to ductless split
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/5/20207/6/20207/6/2020PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by shane miller Corrections made final ok
Rough-In Permanent Service7/1/20207/2/20207/2/2020AFAIL
DetailsJames Ady
Call the above 3 iF NO ANSWER. Phone #: ###-#### Inspection requested via web by shane miller 406.12 Dwelling receps shall be tamper resistant. 406.9A Receps in damp location shall be type WR. 358.42 Couplings and connectors shall be made up tight. 300.9 Interior of raceway above grade in wet location shall be considered a wet location. (Wheather proof recep near A/C romex in conduit, loose connector , Non tamper and non WR,)
Rough-In Permanent Service6/30/20207/1/20207/1/2020ANH
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by shane miller No access reschedule
Issue PAID IN FULL permit  6/30/2020 DONE
Payment received via Govolutions
Application received  6/30/2020 DONE
This permit was created on the web by shane miller