INSP - Permanent service | 8/8/1996 | 8/9/1996 | 8/9/1996 | P | PASS |
Jack Frank
|
|
|
08/09/96 315 - REINSPECTION- CALL OLIVIA HIGGS AT ###-#### AND SHE WILL 53 ok jf cor. made 200a o/h rec.
|
INSP - Permanent service | 8/7/1996 | 8/8/1996 | 8/8/1996 | P | NH |
Jack Frank
|
|
|
08/08/96 315 - CALL OLIVIA HIGGS BEFORE YOU GO OUT -- SORRY THEY DIDN'T GIVE YOU. NALC JF
|
INSP - Permanent service | 8/5/1996 | 8/5/1996 | 8/5/1996 | P | FAIL |
Jack Frank
|
|
|
08/05/96 315 - 53 failed jf cor. posted BCC,4-5-54 no violations to be r bond service properly, 250-80&81(a) grd or bond to metal water piping,200-6(a)&(b) ID neutrals properly, 110-14 use cool aid on alum. w
|
Application received | | | 8/5/1996 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/5/1996 | | |
|
|
|
|
Issue FEE-DUE permit | | | 8/5/1996 | | |
|
|
|
|