INSP - Final | 5/2/1997 | 5/2/1997 | 5/4/1997 | P | PASS |
Marv Burrus
|
|
|
05/02/97 403 - CORRECTIONS COMPLETED...MB
|
INSP - Final | 4/23/1997 | 4/23/1997 | 4/23/1997 | P | FAIL |
Joe Ray
|
|
|
04/23/97 404 - AFTER 2 O'CLOCK panel covers 210-8 kit recpts 210-52 d garage bath 250 garage recpts
|
INSP - Electrical Rough-In | 1/21/1997 | 1/21/1997 | 1/21/1997 | P | PASS |
Marv Burrus
|
|
|
01/21/97 403 - CORRECTION'S COMPLETED..MB
|
INSP - Electrical Rough-In | 1/15/1997 | 1/16/1997 | 1/16/1997 | A | FAIL |
Marv Burrus
|
|
|
01/15/97 403 - NEC: 210-52(D). IN DWELLING UNITS, AT LEAST ONE WALL RECEPTICLE OUTLET SHALL BE INSTALLED IN BATHROOMS ADJACENT TO EACH BASIN LOCATION. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC: 210-8(A)(1). BATHROOMS SHALL HAVE G.F.C.I. PROTECTION FOR PERSONNEL. B.C.C. 1205-C. IN-HOUSE FANS SHALL HAVE A MANUAL SWITCH AND AUTOMATIC TIMER SWITCH.
|
INSP - Electrical Rough-In | 1/15/1997 | 1/15/1997 | 1/15/1997 | P | NH |
Marv Burrus
|
|
|
01/15/97 403 - HE WILL CALL YOU FOR ACCESS RECEIVED NO CALL, NO ACCESS-LEFT CARD...MB
|
INSP - Permanent service | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | PASS |
Marv Burrus
|
|
|
11/25/96 403 -
|
Issue PAID IN FULL permit | | | 8/12/1996 | | |
|
|
|
|
Application received | | | 8/12/1996 | | |
|
|
|
|