INSP - Final | 10/11/1996 | 10/11/1996 | 10/11/1996 | P | PASS |
|
|
|
REINSPECTION
|
INSP - Final | 10/10/1996 | 10/10/1996 | 10/10/1996 | P | FAIL |
|
|
|
reinspection/ as early as possible/ trying to get building final --Now mantel has been removed - no box wired
|
INSP - Final | 10/9/1996 | 10/9/1996 | 10/9/1996 | P | FAIL |
Jack Frank
|
|
|
10/09/96 315 - 14 failed jf cor. posted NEC,210-8 receptacle in garage f needs gfci protection BCC, terminate uf wire in backyard install recepta and plates MB bath
|
Issue PAID IN FULL permit | | | 10/4/1996 | | |
|
|
|
|
INSP - (Pools) bonding | 9/23/1996 | 9/23/1996 | 9/23/1996 | A | PASS |
|
|
|
|
INSP - Permanent service | 8/23/1996 | 8/23/1996 | 9/23/1996 | A | PASS |
|
|
|
|
Issue & PRINT FEE-DUE permit | | | 9/19/1996 | | |
|
|
|
|
INSP - (Pools) bonding | 9/17/1996 | 9/17/1996 | 9/17/1996 | P | FAIL |
|
|
|
GROUND WIRING FOR SWIMMING POOL --depth of #8 copper bond wire only 6"--
|
Issue FEE-DUE permit | | | 9/17/1996 | | FEE |
|
|
|
ADDED SWIMMING POOL TO PERMIT $25.00
|
INSP - Ele Rough-In/Perm Svc | 8/22/1996 | 8/23/1996 | 8/23/1996 | A | FAIL |
|
|
|
300-22-C wire & boxes in cold air return - 370-23 Secure enclosure below panel - 110-16 Access to jetted tub motor & can't see listing - BCE Code 4-5-53-F basement not wired - ---service okay - added inspection for service jms---
|
INSP - Ele Rough-In/Perm Svc | 8/22/1996 | 8/22/1996 | 8/22/1996 | P | FAIL |
|
|
|
No Address
|
Issue FEE-DUE permit | | | 8/22/1996 | | |
|
|
|
|
Application received | | | 8/22/1996 | | |
|
|
|
|