INSP - Final | 8/4/1997 | 8/4/1997 | 8/5/1997 | P | PASS |
Marv Burrus
|
|
|
08/04/97 403 - There will be someone there after 11
|
INSP - Ele Rough-In/Perm Svc | 2/11/1997 | 2/12/1997 | 2/12/1997 | A | PASS |
Pat Lass
|
|
|
02/12/97 336 - ok
|
INSP - Ele Rough-In/Perm Svc | 2/5/1997 | 2/5/1997 | 2/5/1997 | P | FAIL |
Marv Burrus
|
|
|
02/05/97 403 - JOHN WILL CALL TO SCHEDULE ENERGY SAVER CODE:1205 (C). EXHAUST FAN SHALL HAVE TIMER SWITCH AND MAN SWITCH. NEC: 210-52(A). RECPTICLE OUTLET SHALL BE REQUIRED IN EVERY 2F WIDTH OF WALL SPACE. NEC: 210-52(D). BATHROOM RECEPTICLE OUTLETS SHALL SHALL HAVE NO OTHER OUTLETS. NEC: 250-113. SHEET METEL SCREWS SHALL NOT BE USED TO CONNECT GROUNDING CONDUCTERS.
|
Application received | | | 9/19/1996 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/19/1996 | | |
|
|
|
|