Receive PAYMENT IN FULL | | | 7/11/1997 | | |
|
|
|
|
INSP - Hot Tubs/Spas | 7/9/1997 | 7/9/1997 | 7/9/1997 | P | PASS |
Pat Lass
|
|
|
07/09/97 336 - he said final but hot tub not approved ok
|
INSP - Final | 7/9/1997 | 7/9/1997 | 7/9/1997 | P | PASS |
Pat Lass
|
|
|
07/09/97 336 - he called for a final but i see perm service and hot tub them so i put 3 different inspections in. hot tub, service and final ok
|
INSP - Permanent service | 7/9/1997 | 7/9/1997 | 7/9/1997 | P | PASS |
Pat Lass
|
|
|
07/09/97 336 - he said final but i see perm service not approved ok
|
INSP - Permanent service | 6/20/1997 | 6/25/1997 | 6/25/1997 | A | FAIL |
Pat Lass
|
|
|
06/25/97 336 - disapproved 210-4 250-92 (b)
|
INSP - Hot Tubs/Spas | 6/20/1997 | 6/25/1997 | 6/25/1997 | A | FAIL |
Pat Lass
|
|
|
06/25/97 336 - disapproved 680-6(a) 680-12
|
Issue & PRINT FEE-DUE permit | | | 6/19/1997 | | |
|
|
|
|
Application received | | | 6/19/1997 | | |
|
|
|
|