Receive PAYMENT IN FULL | | | 8/7/1997 | | |
|
|
|
|
INSP - Permanent service | 7/15/1997 | 7/15/1997 | 7/15/1997 | P | PASS |
Marv Burrus
|
|
|
07/15/97 403 - reinspection. CORRECTIONS COMPLETED...MB
|
INSP - Permanent service | 7/11/1997 | 7/14/1997 | 7/14/1997 | A | FAIL |
Jack Frank
|
|
|
07/14/97 315 - REINSPECTION 53 failed cor. posted NEC, 250-23, 91(a) e 110-3(b)
|
(F) Reprint permit | | | 7/10/1997 | | |
|
|
|
|
INSP - Permanent service | 7/9/1997 | 7/9/1997 | 7/9/1997 | P | FAIL |
Jack Frank
|
|
|
07/09/97 315 - 53 failed jf cor. posted NEC, 110-14 needs kool aid on al clearence for new panels a&b 250-92(b) GEC needs connector or non metall bushings, 250-81 grd to metal water system, 250-94 needs 1/0 cu. or 3/0
|
Application received | | | 7/9/1997 | | |
|
|
|
|
Issue & PRINT FEE-DUE permit | | | 7/9/1997 | | |
|
|
|
|