Receive PAYMENT IN FULL | | | 10/28/1997 | | |
|
|
|
|
INSP - Final | 9/9/1997 | 9/9/1997 | 9/9/1997 | P | PASS |
Marv Burrus
|
|
|
DOES THIS REALLY ONLY HAVE 5 ROOMS? MONICA has 7 rooms....mb
|
(F) Reprint permit | | | 9/9/1997 | | |
|
|
|
|
Change status to Fee Due | | | 9/9/1997 | | |
|
|
|
|
Receive PAYMENT IN FULL | | | 9/4/1997 | | |
|
|
|
|
INSP - Permanent service | 8/14/1997 | 8/14/1997 | 8/14/1997 | P | PASS |
Jim Schmer
|
|
|
|
INSP - Ele Rough-In/Perm Svc | 8/8/1997 | 8/8/1997 | 8/8/1997 | P | PART |
Jim Schmer
|
|
|
pouring concrete p.m.
|
INSP - Ele Rough-In/Perm Svc | 8/5/1997 | 8/5/1997 | 8/5/1997 | P | FAIL |
Marv Burrus
|
|
|
08/05/97 403 - NEC:230-6. PVC CONDUIT FROM METER INSIDE GARAGE FOR SERVICE ENTRANCE CONDUCTORS SHALL NOT BE ALLOWED. NEC: 333-12. CABLES WITHIN 6FT OF ATTIC ACCESS SHALL BE PROTECTED. BOISE CITY ENERGY CODE 1205-C. TIMER AND MANUAL SWITCH FOR IN HOUSE FAN REQUIRED.
|
Issue & PRINT FEE-DUE permit | | | 8/4/1997 | | |
|
|
|
|
Application received | | | 8/4/1997 | | |
|
|
|
|