Receive PAYMENT IN FULL | | | 10/29/1997 | | |
|
|
|
|
INSP - Permanent service | 8/14/1997 | 8/14/1997 | 8/14/1997 | P | PASS |
Jack Frank
|
|
|
08/14/97 315 - 53 ok jf o/h rec.
|
Application received | | | 8/11/1997 | | |
|
|
|
|
Issue & PRINT FEE-DUE permit | | | 8/11/1997 | | |
|
|
|
|
INSP - Permanent service | 8/11/1997 | 8/11/1997 | 7/22/1997 | P | FAIL |
Jack Frank
|
|
|
08/11/97 315 - this is for the existing building no structural permit. $ 53 failed jf cor. posted NEC 230-6 service raceway shall be outside of building or encased in 2 inches of concrete or brick to be considered ou of building as code states
|