INSP - Final | 10/27/1997 | 10/27/1997 | 10/27/1997 | P | PASS |
Marv Burrus
|
|
|
10/27/97 403 - REIN CORRECTIONS COMPLETED.
|
INSP - Final | 10/20/1997 | 10/20/1997 | 10/20/1997 | P | FAIL |
Marv Burrus
|
|
|
NEC: 410-8(D)(1)&(2). LIGHT FIXTURE IN CLOSET SHALL BE 12IN. FROM EDGE OF SHELF; INCANDESCENT FIXTURE SHALL HAVE PROTECTIVE COVER.
|
INSP - Permanent service | 10/7/1997 | 10/8/1997 | 10/8/1997 | P | PASS |
Marv Burrus
|
|
|
10/08/97 403 - Please do this AM - jms
|
INSP - Permanent service | 9/29/1997 | 9/30/1997 | 9/30/1997 | A | CANC |
Marv Burrus
|
|
|
09/29/97 403 - WANTED GROUND WORK FOR PERM/SVC ONLY.
|
INSP - Ground work | 9/30/1997 | 9/30/1997 | 9/30/1997 | | PASS |
Marv Burrus
|
|
|
/ / 403 - CONCRETE ENCASED ELECTRODE.
|
Receive PAYMENT IN FULL | | | 9/12/1997 | | |
|
|
|
|
INSP - Ele Rough-In/Perm Svc | 8/26/1997 | 8/27/1997 | 8/27/1997 | P | FAIL |
Marv Burrus
|
|
|
08/27/97 403 - NO GROUNDING UFER. NEC: 250-81(C). GROUNDING ELECTRODE THAN NO.#4 COPPER AND 20FT. IN LENGTH, SHALL BE INCASED IN 2IN. OF CONCRETE.
|
INSP - Electrical Rough-In | 8/27/1997 | 8/27/1997 | 8/27/1997 | | PASS |
Marv Burrus
|
|
|
/ / 403 - WALLS OK TO COVER.
|
Application received | | | 8/21/1997 | | |
|
|
|
|
Issue & PRINT FEE-DUE permit | | | 8/21/1997 | | |
|
|
|
|