INSP - Electrical Rough-In | 4/7/1999 | 4/7/1999 | 4/7/1999 | P | PASS |
Marv Burrus
|
|
|
04/07/99 403 - ###-#### ROCK//AFTER 3:30 HOT TUB ONLY REINSPECTION CORRECTIONS COMPLETED. OK
|
INSP - Final | 3/31/1999 | 4/1/1999 | 4/1/1999 | A | FAIL |
Marv Burrus
|
|
|
03/31/99 403 - ###-#### ERIC//HOT TUB ONLY FINAL PANELBOARD DISCONNECT AT HOT TUB NOT USED; DISCONNECT WAS A/C UNIT PULL- GFCI RECEPTICLE NOT AT LEAST 10 FT. FROM HOT TUB.
|
INSP - Final | 1/22/1999 | 1/22/1999 | 1/22/1999 | P | PASS |
Marv Burrus
|
|
|
01/22/99 403 - eric ###-#### re-insp fn insp CORRECTIONS COMPLETED. OK
|
INSP - Final | 1/21/1999 | 1/22/1999 | 1/22/1999 | A | FAIL |
Marv Burrus
|
|
|
01/21/99 403 - ERIC ###-#### NEC: 370-19. RECEPTICLE OUTLET BOX SHALL HAVE DEVICE. NEC: 370-20. OUTLET BOX SHALL BE NO MORE THAN 1/4IN FROM FINISHED SURFA
|
INSP - Electrical Rough-In | 9/25/1998 | 9/28/1998 | 9/28/1998 | A | PASS |
Marv Burrus
|
|
|
09/27/98 403 - perm service
|
INSP - Electrical Rough-In | 9/25/1998 | 9/25/1998 | 9/25/1998 | | PART |
Jack Frank
|
|
|
/ / 315 - conference with Eric about p/s
|
INSP - Electrical Rough-In | 9/25/1998 | 9/25/1998 | 9/25/1998 | | PART |
Jack Frank
|
|
|
/ / 315 - conference with Eric about p/s
|
INSP - Electrical Rough-In | 9/25/1998 | 9/25/1998 | 9/25/1998 | | PART |
Jack Frank
|
|
|
/ / 315 - conference with Eric about p/s
|
INSP - Electrical Rough-In | 9/25/1998 | 9/25/1998 | 9/25/1998 | | PART |
Jack Frank
|
|
|
/ / 315 - conference with Eric about p/s
|
INSP - Electrical Rough-In | 9/17/1998 | 9/17/1998 | 9/17/1998 | | PART |
Jack Frank
|
|
|
/ / 315 - 01 with Centers concerning NEC, 250-61
|
INSP - Electrical Rough-In | 9/14/1998 | 9/15/1998 | 9/15/1998 | A | PART |
Marv Burrus
|
|
|
09/15/98 403 - ERIC ###-#### SERVICE PANELBOARD NOT READY. ELE R/I OK.
|
Receive PAYMENT IN FULL | | | 7/14/1998 | | |
|
|
|
|
INSP - Electrical Rough-In | 6/26/1998 | 6/26/1998 | 6/26/1998 | A | CANC |
Jim Schmer
|
|
|
ufer ground/eric ###-#### early asap please..covered before inspection..
|
INSP - Electrical Rough-In | 6/24/1998 | 6/25/1998 | 6/25/1998 | A | FAIL |
Joe Ray
|
|
|
06/25/98 404 - concrete electro ufer inspection/eric ###-####..trans jms ufer not in called contr. no answer
|
Issue & PRINT FEE-DUE permit | | | 6/24/1998 | | |
|
|
|
|
Application received | | | 6/24/1998 | | |
|
|
|
|