Electrical Rough-In | 10/29/2002 | 10/29/2002 | 10/29/2002 | P | PASS |
Tim McCullough
|
|
|
###-#### ERIC
finnal ok 10/29/2002 1:09:42 PM
|
DOC - Permit Finaled | 10/29/2002 | 10/29/2002 | 10/29/2002 | P | PASS |
Tim McCullough
|
|
|
Finaled by inspector at 10/29/2002 1:09:45 PM
|
Electrical Rough-In | 10/23/2002 | 10/23/2002 | 10/23/2002 | P | PART |
Jim Schmer
|
|
|
conference about corrections on grd. cond. not long enough. 10/23/2002 2:55:06 PM
|
Electrical Rough-In | 10/21/2002 | 10/22/2002 | 10/22/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### ERIC corrections not made still needs 6 inches free length of conductor ged wires cut short only 11/2 to 2 inches long 10/22/2002 12:26:07 PM
|
Electrical Rough-In | 10/3/2002 | 10/3/2002 | 10/3/2002 | P | FAIL |
Jack Frank
|
|
|
FOR CONF -###-#### ERIC- STATUS IS EXPIRED??? conference ok but has box fill and all conductor shall have 6 inches free length at all boxes 10/3/2002 4:52:08 PM
|
Electrical Rough-In | 9/30/2002 | 10/1/2002 | 10/1/2002 | A | NR |
Pat Lass
|
|
|
ERIC ###-####
Had conf. 10/1/2002 10:22:42 AM
|
Final | 9/27/2002 | 9/27/2002 | 9/27/2002 | P | PART |
Jack Frank
|
|
|
dropped correction notice off
|
Final | 9/25/2002 | 9/26/2002 | 9/26/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. posted based on 1996 NEC 410-8, 210-52 (a)(b) (c) outlet spacing for countertops in kit, wall space MBed, all outlets in closet shall be on bathrm circuit with gfci because closet is part of MB bath, remove panel from bathrm, closet, open all walls covered before inspection, this job is 4 years old owner only had 2 partial inspection this job is a nightmare because owner dropped the ball see jf for details 9/26/2002 6:36:43 PM
|
Final | 9/26/2002 | 9/26/2002 | 9/26/2002 | A | FAIL |
Jack Frank
|
|
|
will post correction need to go back to 1996 nec for correction this job is a mess owner never called for all required inspection
|
INSP - Electrical Rough-In | 9/25/1998 | 9/28/1998 | 9/28/1998 | A | PART |
Jack Frank
|
|
|
09/28/98 315 - ok ERIC ###-####
|
Permit EXPIRED | | | 9/28/1998 | | PASS |
|
|
|
|
INSP - Electrical Rough-In | 9/22/1998 | 9/23/1998 | 9/23/1998 | P | PART |
Jack Frank
|
|
|
09/23/98 315 - eric ###-#### partial rough in ok for partial r/i and conference was there 1hour and 15 min.
|
(F) Reprint permit | | | 7/8/1998 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/8/1998 | | |
|
|
|
|
Application received | | | 7/8/1998 | | |
|
|
|
|