DOC - Permit Finaled | 1/10/2002 | 1/10/2002 | 1/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/10/2002 2:47:32 PM
|
INSP-Final Inspection | 7/7/2000 | 7/11/2000 | 7/11/2000 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/07/2000 at 11:05:57. Contact: ###-####.; trip test fpr dry system okay; tampers needed on anti-freeze system;
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2000 | 7/10/2000 | 7/10/2000 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/05/2000 at 09:19:26. Contact: ###-####. Hydro-ok 7/11/00 11:38:43 AM
|
INSP-Conference | 5/25/2000 | 5/25/2000 | 5/25/2000 | P | PART |
Rick Jackson
|
|
|
met with Lynn about obstructed heads in main store; canopies over 4 ft require heads; sway bracing needed. c/n issued on 5/24 to general contractor about the above
|
Issue permit | | | 5/23/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 5/22/2000 | 5/22/2000 | 5/22/2000 | | DONE |
|
|
|
|
Telephone call | | | 5/22/2000 | | DONE |
|
|
|
talked to treasa gave dollar amount
|
Sprinkler Plan Check | 5/11/2000 | | 5/18/2000 | | PASS |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 1/12/2000 | | 2/2/2000 | | FAIL |
|
|
|
Calculation and water supply problems needing correcting. Some mains calculated larger than what is shown on the plans.
|
Telephone call | | | 2/2/2000 | | FAIL |
|
|
|
Faxed a copy of the review to Shilo. Awaiting response.
|
Application received | | | 1/12/2000 | | PASS |
|
|
|
|
Telephone call | | | | | PEND |
Bill Alexander
|
|
|
|
Miscellaneous action | | | | | PEND |
Bill Alexander
|
|
|
|
Case Summary | | | | | PASS |
Bill Alexander
|
|
|
|