DOC - Permit Finaled | 2/13/2002 | 2/13/2002 | 2/13/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/13/2002 9:08:06 AM
|
INSP-Final Inspection | 5/17/2000 | 5/17/2000 | 5/17/2000 | P | PASS |
Rick Jackson
|
|
|
All complete; alarms working. 5/18/00 3:11:19 PM
|
INSP-Sprinkler Rough-in | 4/28/2000 | 4/28/2000 | 4/28/2000 | | FAIL |
Rick Jackson
|
|
|
r/i with Shilo - all items on JWA's c/n were corrected. alarms/tampers not complete. one hanger by east stair in basement not attched pending installation of stairs
|
Sprinkler Plan Check | 4/10/2000 | | 4/17/2000 | | PASS |
Bill Alexander
|
|
|
Area remote for the main level verified by calculations to be increased from 120 sq. ft. per head to 127 sq. ft. per head.
|
Telephone call | | | 4/17/2000 | | PASS |
Bill Alexander
|
|
|
Revised calculation change (review notes) faxed to Shilo.
|
INSP-Sprinkler Rough-in/Hydro | 4/4/2000 | 4/5/2000 | 4/5/2000 | P | FAIL |
Rick Jackson
|
|
|
###-#### *JWA* Lines/heads both in the basement and main level are overspaced for system design spacing. Lack coverage in some partition "coves". Main floor line sprinklers on the south side are all below 6" from bottom of joists or 18" from roof deck maximum allowance. Heads overspaced (120 sq ft. per head) under east entry (basement).
|
INSP-Supply line flush | 3/14/2000 | 3/14/2000 | 3/14/2000 | A | PASS |
Rick Jackson
|
|
|
|
INSP-Sprinkler Rough-in | 2/10/2000 | 2/10/2000 | 2/10/2000 | P | PART |
Rick Jackson
|
|
|
okay to cover first flor corridor
|
Inspection Record Card- Bld | 1/25/2000 | 1/25/2000 | 1/25/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 1/25/2000 | 1/25/2000 | 1/25/2000 | | DONE |
|
|
|
|
Telephone call | | | 1/25/2000 | | DONE |
|
|
|
talked to cathy gave dollar amount
|
Issue permit | | | 1/25/2000 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/25/2000 | | PASS |
|
|
|
PLANS TAKEN TO THE FRONT DESK FOR CALLING AND DISTRIBUTION
|
Telephone call | | | 1/24/2000 | | PASS |
|
|
|
Called Shilo (talked to Bob Knight). Cover sheet indicates "Retail" for lower level and calculated at .15 (Ordinary Group 1) which is not "Retail", but limited misc. storage under 8-0, and not exceeding the limitations of miscellaneous storage.
|
Sprinkler Plan Check | 1/7/2000 | | 1/24/2000 | | PASS |
|
|
|
|
Application received | | | 1/7/2000 | | PASS |
|
|
|
|
Case Summary | | | | | PASS |
|
|
|
|