DOC - Permit Finaled | 1/10/2002 | 1/10/2002 | 1/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/10/2002 3:10:41 PM
|
INSP-Final Inspection | 5/26/2000 | 5/26/2000 | 5/26/2000 | P | FAIL |
Rick Jackson
|
|
|
Aaron ###-#### Not a final- hydro test ok. 5/30/00 3:39:13 PM
|
INSP-Supply line flush | 5/24/2000 | 5/24/2000 | 5/24/2000 | P | PASS |
Rick Jackson
|
|
|
flush okay
|
INSP-Sprinkler Rough-in | 5/24/2000 | 5/24/2000 | 5/24/2000 | A | PART |
Rick Jackson
|
|
|
okay to cover griided ceiling areas only. earthquaking on mains must go to beams and not walls
|
Issue permit | | | 3/13/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 3/10/2000 | 3/10/2000 | 3/10/2000 | | DONE |
|
|
|
|
Telephone call | | | 3/10/2000 | | DONE |
|
|
|
called gave dollar amount
|
Sprinkler Plan Check | 3/6/2000 | | 3/10/2000 | | PASS |
Bill Alexander
|
|
|
Some questions need response to and updating on submittals for completion. Delayed submittals will be accepted.
|
Telephone call | | | 3/10/2000 | | PASS |
Bill Alexander
|
|
|
COPY OF REVIEW FAXED.
|
Miscellaneous action | | | 3/10/2000 | | PASS |
Bill Alexander
|
|
|
PLANS TAKEN TO FRONT DESK FOR ACLLING, FEE COLLECTION AND PERMIT LETTING.
|
Application received | | | 3/6/2000 | | PASS |
Bill Alexander
|
|
|
OVERHEAD PIPING AND CALCULATIONS
|
Application received | | | 1/24/2000 | | PASS |
|
|
|
UNDERGROUND PRELIMINARY PLAN SUBMITTAL FOR MATERIALS, INSTALLATION, FLUSH AND TEST PER NFPA 24.
|
Sprinkler Plan Check | 1/24/2000 | | 1/24/2000 | | PASS |
|
|
|
UNERGROUND PLANS SHOWING LOCATION ONLY. REFERENCE NOTES.
|
Telephone call | | | 1/24/2000 | | PASS |
|
|
|
FAXED PLAN REVIEW, COPY TO RICH JACKSONS MAIL BOX.
|
Case Summary | | | | | PASS |
Bill Alexander
|
|
|
|