Permit Information
Permit NumberFIR00-00021
StatusFinaled
Name TREASURE VALLEY FIRE
Site Address 2910 E AMITY RD
Project NameSPR UG TRUS JOIST MACM.
Customer Number 
ePlanReview 
Description
TRUS JOIST MACMILLAN (PHASE IIB OF TECHNOLOGY CENTER PROJECT)* TO FIRE SPRINKLER A 27,295 SQUARE FOOT, 2 STORY, WOOD FRAME OFFICE ADDITION AT THE NORTH END OF THE TECHNOLOGY CENTER PLANT FACILITY PRESENTLY UNDER CONSTRUCTION UNDER AN ADA COUNTY BUILDING PERMIT. THIS BUILDING IS FULLY FIRE SPRINKLED. THE SPRINKLERS ARE BEING USED FOR UNLIMITED AREA WITH MINIMUM 60 FOOT ADJOINING YARDS ENTIRELY SURROUNDING THE TECHNOLOGY CENTER. ALL WORK PER UFC, THE APPROVED PLANS, ATTACHED REQUIREMENT LIST AND BOISE FIRE DEPARTMENT. THIS PERMIT ALSO INCLUDES RELATED UNDERGROUND SUPPLY.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled1/10/20021/10/20021/10/2002PPASS
DetailsRick Jackson
Finaled by inspector at 1/10/2002 3:10:41 PM
INSP-Final Inspection5/26/20005/26/20005/26/2000PFAIL
DetailsRick Jackson
Aaron ###-#### Not a final- hydro test ok. 5/30/00 3:39:13 PM
INSP-Supply line flush5/24/20005/24/20005/24/2000PPASS
DetailsRick Jackson
flush okay
INSP-Sprinkler Rough-in5/24/20005/24/20005/24/2000APART
DetailsRick Jackson
okay to cover griided ceiling areas only. earthquaking on mains must go to beams and not walls
Issue permit  3/13/2000 DONE
Inspection Record Card- Bld3/10/20003/10/20003/10/2000 DONE
Telephone call  3/10/2000 DONE
called gave dollar amount
Sprinkler Plan Check3/6/2000 3/10/2000 PASS
DetailsBill Alexander
Some questions need response to and updating on submittals for completion. Delayed submittals will be accepted.
Telephone call  3/10/2000 PASS
DetailsBill Alexander
COPY OF REVIEW FAXED.
Miscellaneous action  3/10/2000 PASS
DetailsBill Alexander
PLANS TAKEN TO FRONT DESK FOR ACLLING, FEE COLLECTION AND PERMIT LETTING.
Application received  3/6/2000 PASS
DetailsBill Alexander
OVERHEAD PIPING AND CALCULATIONS
Application received  1/24/2000 PASS
UNDERGROUND PRELIMINARY PLAN SUBMITTAL FOR MATERIALS, INSTALLATION, FLUSH AND TEST PER NFPA 24.
Sprinkler Plan Check1/24/2000 1/24/2000 PASS
UNERGROUND PLANS SHOWING LOCATION ONLY. REFERENCE NOTES.
Telephone call  1/24/2000 PASS
FAXED PLAN REVIEW, COPY TO RICH JACKSONS MAIL BOX.
Case Summary    PASS
DetailsBill Alexander