INSP-Final Inspection | 8/13/2001 | 8/13/2001 | 8/13/2001 | A | PASS |
Joe Tawney
|
|
|
Added by Inspector: 406 On 8/13/2001 8:19:44 AM
|
DOC - Permit Finaled | 8/13/2001 | 8/13/2001 | 8/13/2001 | A | PASS |
Joe Tawney
|
|
|
Finaled by inspector at 8/13/2001 8:19:50 AM
|
DOC - Permit Finaled | 5/9/2001 | 5/9/2001 | 5/9/2001 | P | PASS |
Joe Tawney
|
|
|
Finaled by inspector at 5/9/2001 2:48:52 PM
|
Telephone call | | | 1/4/2001 | | DONE |
|
|
|
Shilo called and faxed a sprinkler spacing problem over the display coolers (on one side of soffit/wall and freezer/cooler storage. My response was verbal in meeting the requirements that if the store can provide and apporoved control system from andy storage, the non combustible area will then require no sprinkler coverage.
|
INSP-Sprinkler Rough-in | 12/29/2000 | 12/29/2000 | 12/29/2000 | A | FAIL |
Joe Tawney
|
|
|
Added by Inspector: 406 On 12/29/2000 2:39:37 PM Spklr rough in West side. Fail Four items to correct
|
INSP-Sprinkler Rough-in/Hydro | 12/27/2000 | 12/28/2000 | 12/28/2000 | P | PART |
Joe Tawney
|
|
|
###-####. OK on hydro test of new spklr system for West side of bldg 12/29/2000 2:31:28 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/15/2000 | 11/15/2000 | 11/15/2000 | P | PART |
Joe Tawney
|
|
|
###-####. OK spklr rough in on McDonalds and hydro test of riser #4 11/16/2000 7:59:16 AM
|
Issue permit | | | 11/8/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 11/7/2000 | 11/7/2000 | 11/7/2000 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/6/2000 | 11/7/2000 | 11/7/2000 | P | PART |
Joe Tawney
|
|
|
###-####. OK on both entry ways 11/8/2000 8:02:17 AM
|
Telephone call | | | 11/7/2000 | | DONE |
|
|
|
called permit ready
|
Sprinkler Plan Check | 11/6/2000 | | 11/6/2000 | | PASS |
Bill Alexander
|
|
|
Plan Modification submittal
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/6/2000 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 11/6/2000 | | DONE |
|
|
|
Copy of review notes faxed to Shilo - plans are ready!
|
INSP-Final Inspection | 11/2/2000 | 11/3/2000 | 11/3/2000 | P | FAIL |
Joe Tawney
|
|
|
###-####. 11/2/2000 12:30:02 PM Fail on rough in of new West entry.Resubmittal required 11/6/2000 7:57:31 AM
|
Sprinkler Plan Check | 8/1/2000 | | 8/2/2000 | | FAIL |
Bill Alexander
|
|
|
FRONT ENTRY respaced heads to exceed design spacing calculation verification failed due to questions of room design method as submitted.
|
INSP-Final Inspection | 7/28/2000 | 7/31/2000 | 7/31/2000 | A | FAIL |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 07/28/2000 at 13:36:38. Contact: ###-####. REinsp. fail entry way visable over spaces 7/31/00 4:31:23 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/26/2000 | 7/27/2000 | 7/27/2000 | A | PART |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 07/26/2000 at 16:28:35. Contact: ###-####. OK on hydro test for subs area C/N issued for spklr. R/I 7/27/00 1:54:40 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/25/2000 | 7/26/2000 | 7/26/2000 | A | FAIL |
Joe Tawney
|
|
|
ANN-- ###-#### HYDRO Not ready reschedule to 7/27/00 7/26/00 1:16:17 PM
|
Telephone call | | | 6/30/2000 | | DONE |
|
|
|
called shelly gave her dollar amount
|
Inspection Record Card- Bld | 6/30/2000 | 6/30/2000 | 6/30/2000 | | DONE |
|
|
|
|
Issue permit | | | 6/30/2000 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/28/2000 | | 6/29/2000 | | PART |
Bill Alexander
|
|
|
THIS IS A PARTIAL APPROVAL. Need seperate fire hose station review and water supply information verification noted on review notes.
|
Telephone call | | | 6/29/2000 | | DONE |
|
|
|
Faxed copy of review to designer and architects office since relating to UFC Article 81 issues now must be verified.
|
Miscellaneous action | | | 6/29/2000 | | DONE |
|
|
|
Plans taken to the front desk for calling, fee collection and permitting.
|
INSP-Sprinkler Rough-in | 6/28/2000 | 6/28/2000 | 6/28/2000 | P | PART |
Joe Tawney
|
|
|
Ann ###-#### ok on partial garden area spklr rough in 6/29/00 10:10:14 AM
|
Telephone call | | | 6/22/2000 | | DONE |
Bill Alexander
|
|
|
Faxed copy of 2nd review to the designer
|
Telephone call | | | 6/8/2000 | | DONE |
Bill Alexander
|
|
|
Received Cover sheets. Called designer: R. Lopez. Need calculation design criteria system meets for remote area #1. .30/2000 (by owner) is not specific for commodity classification, height, NFPA 231, 231C, minimum requirements meeting? Need figure, curve, aisle widths, racking type, open, closed, palletized, conventional pallets or plastic, solid shelving or open? Require clearer an more specific information. Faxed "Failed" review after finding mistakes in node identification and pipe sizes not correlating with plans and calculations.
|
Telephone call | | | 6/8/2000 | | DONE |
Bill Alexander
|
|
|
Called and requested cover sheets. Questioned underground connection of water supply. Calculations do not indicate connection of water supply at the same pont as plans. Need verification.
|
Sprinkler Plan Check | 6/6/2000 | | 6/6/2000 | | FAIL |
Bill Alexander
|
|
|
|
Telephone call | | | 6/6/2000 | | DONE |
Bill Alexander
|
|
|
Faxed copy of 2nd review to designer.
|
Sprinkler Plan Check | 4/18/2000 | | 4/27/2000 | | FAIL |
Bill Alexander
|
|
|
To many problems to continue. Requesting a complete designer review.
|
Application received | | | 4/26/2000 | | FAIL |
Bill Alexander
|
|
|
Require Cover Sheet for design requirements. No information provided on the plans or calculations that verify design requirememtns.
|