Permit Information
Permit NumberFIR00-00275
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 621 S 17TH ST
Project NameSPR BEAVER RIVER POWER
Customer Number 
ePlanReview 
Description
(BEAVER RIVER POWER COMPANY BUILDING) This building is being fire sprinklered to substitute for 1-hr fire-resistive construction. To fire sprinkler this buildings shell and core. A mechanical mezzanine is also expanded by 225 square feet. Work is to include installation per UFC, related NFPA, Boise Fire department the approved plans and attached review condition notes. Tenant improvement permits shall be applied for separately. This permit does not establish a Certificate of Occupancy for any tenant. BLD99-0314 *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  10/5/2016 DONE
DOC - Permit Finaled5/31/20015/31/20015/31/2001APASS
DetailsRick Jackson
Finaled by inspector at 5/31/2001 8:30:22 AM
INSP-Final Inspection5/31/20015/31/20015/31/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 5/31/2001 8:29:45 AM
INSP-Sprinkler Rough-in/Hydro10/16/200010/17/200010/17/2000PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/16/2000 at 15:46:45. Contact: ###-####. r/i and hydro okay; heads painted on 2nd floor 10/18/2000 10:00:30 AM
Issue permit  9/7/2000 DONE
Sprinkler Plan Check9/4/2000 9/5/2000 PASS
DetailsBill Alexander
Resubmittal of overhead system.
Inspection Record Card- Bld9/5/20009/5/20009/5/2000 DONE
Telephone call  9/5/2000 DONE
talked to becky gave dollar amount
PLANS/APPL TAKEN TO FRONT DESK  9/5/2000 PASS
DetailsBill Alexander
INSP-Sprinkler Rough-in8/31/20009/1/20009/1/2000APASS
DetailsRick Jackson
underground test insp De Best Fire Protection ###-#### undergound hydro okay. plans not on site - Debest will ensure they are on-site for any future inspections 9/1/2000 9:14:45 AM
INSP-Supply line flush8/28/20008/29/20008/29/2000PPASS
DetailsRick Jackson
CHRIS-- CELL ###-#### SUPPLY LINE flush okay 8/29/2000 12:12:20 PM
INSP-Sprinkler Rough-in5/24/20005/25/20005/25/2000AFAIL
DetailsRick Jackson
underground Nat ###-#### Need thermal protection for underground main due to depth of bury at 2.5 ft. 5/25/00 1:42:09 PM
Sprinkler Plan Check5/4/2000 5/16/2000 FAIL
DetailsBill Alexander
Lines/heads overspaced.
Telephone call  5/16/2000 DONE
DetailsBill Alexander
O.H failed. Called Bob Knight (new contact for this project) and pointed out deficiencies. Indicated I need resubmittal of sheet 2 of 2 and calcs.
Sprinkler Plan Check5/4/2000 5/15/2000 PASS
DetailsBill Alexander
Underground supply line only.
Telephone call  5/15/2000 PASS
DetailsBill Alexander
Faxed approved copy of underground plan review to Bob Knight.
Application received  5/4/2000 PASS
DetailsBill Alexander
Miscellaneous action    PEND
DetailsBill Alexander
Plans taken to the front desk for calling, fee collection and permitting.