Case Summary | | | 10/5/2016 | | DONE |
|
|
|
|
DOC - Permit Finaled | 5/31/2001 | 5/31/2001 | 5/31/2001 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/31/2001 8:30:22 AM
|
INSP-Final Inspection | 5/31/2001 | 5/31/2001 | 5/31/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 5/31/2001 8:29:45 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2000 | 10/17/2000 | 10/17/2000 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/16/2000 at 15:46:45. Contact: ###-####. r/i and hydro okay; heads painted on 2nd floor 10/18/2000 10:00:30 AM
|
Issue permit | | | 9/7/2000 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/4/2000 | | 9/5/2000 | | PASS |
Bill Alexander
|
|
|
Resubmittal of overhead system.
|
Inspection Record Card- Bld | 9/5/2000 | 9/5/2000 | 9/5/2000 | | DONE |
|
|
|
|
Telephone call | | | 9/5/2000 | | DONE |
|
|
|
talked to becky gave dollar amount
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/5/2000 | | PASS |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in | 8/31/2000 | 9/1/2000 | 9/1/2000 | A | PASS |
Rick Jackson
|
|
|
underground test insp De Best Fire Protection ###-#### undergound hydro okay. plans not on site - Debest will ensure they are on-site for any future inspections 9/1/2000 9:14:45 AM
|
INSP-Supply line flush | 8/28/2000 | 8/29/2000 | 8/29/2000 | P | PASS |
Rick Jackson
|
|
|
CHRIS-- CELL ###-#### SUPPLY LINE flush okay 8/29/2000 12:12:20 PM
|
INSP-Sprinkler Rough-in | 5/24/2000 | 5/25/2000 | 5/25/2000 | A | FAIL |
Rick Jackson
|
|
|
underground Nat ###-#### Need thermal protection for underground main due to depth of bury at 2.5 ft. 5/25/00 1:42:09 PM
|
Sprinkler Plan Check | 5/4/2000 | | 5/16/2000 | | FAIL |
Bill Alexander
|
|
|
Lines/heads overspaced.
|
Telephone call | | | 5/16/2000 | | DONE |
Bill Alexander
|
|
|
O.H failed. Called Bob Knight (new contact for this project) and pointed out deficiencies. Indicated I need resubmittal of sheet 2 of 2 and calcs.
|
Sprinkler Plan Check | 5/4/2000 | | 5/15/2000 | | PASS |
Bill Alexander
|
|
|
Underground supply line only.
|
Telephone call | | | 5/15/2000 | | PASS |
Bill Alexander
|
|
|
Faxed approved copy of underground plan review to Bob Knight.
|
Application received | | | 5/4/2000 | | PASS |
Bill Alexander
|
|
|
|
Miscellaneous action | | | | | PEND |
Bill Alexander
|
|
|
Plans taken to the front desk for calling, fee collection and permitting.
|
Case Summary | | | | | DONE |
|
|
|
|