DOC - Permit Finaled | 4/19/2001 | 4/19/2001 | 4/19/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 4/19/2001 8:54:20 AM
|
INSP-Final Inspection | 3/2/2001 | 3/2/2001 | 3/2/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 3/2/2001 3:52:54 PM
|
INSP-Alarm Testing | 2/15/2001 | 2/16/2001 | 2/16/2001 | A | FAIL |
Rick Jackson
|
|
|
###-#### need detector at damper in north relocated to top of opening; couldn't sprinkler alarms and tampers; 2/16/2001 2:10:53 PM
|
Issue permit | | | 1/5/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 9/28/2000 | 9/28/2000 | 9/28/2000 | | DONE |
|
|
|
|
Telephone call | | | 9/28/2000 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/27/2000 | | |
|
|
|
2nd set of plans received a9/27/00, stamped for jobsite.
|
Alarm Plan Check | 9/25/2000 | | 9/25/2000 | | PASS |
|
|
|
Approved.
|
Alarm Plan Check | 9/13/2000 | | 9/20/2000 | | FAIL |
|
|
|
Calc's incorrect. Discussed by phone with Alarmco.
|
Alarm Plan Check | 8/22/2000 | | 8/28/2000 | | FAIL |
|
|
|
Review of resubmittal faxed 8/22. Two items corrected but battery calc's still not correct. Discussed by phone with Alarmco, Mike McKague.
|
Alarm Plan Check | 8/9/2000 | | 8/18/2000 | | FAIL |
|
|
|
resubmittal received 8/9/00. Faxed review comments to Alarmco.
|
Alarm Plan Check | 6/27/2000 | | 7/5/2000 | | FAIL |
|
|
|
faxed review to Alarmco
|
Application received | | | 7/3/2000 | | |
|
|
|
Note: this is a RESUBMITTALl of plans reviewed 4/29/2000 submitted by Simplex.
|
Case Summary | | | | | |
|
|
|
|