Permit Information
Permit NumberFIR00-00433
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 FEDERAL WAY
Project NameMIC #32 (PCS 3400) TRAILER
Customer Number 
ePlanReview 
Description
MICRON BUILDING #32 TEMPORARY OFFICE TRAILERS (01-11-003400) * TO PLACE TWO 36' X 60' (2130 SQ. FT.) ONE STORY RELOCATABLE OFFICE BUILDINGS. TO BE LOCATED EAST OF THREE EXISTING RELOCATABLE OFFICE TRAILERS AT THE EAST SIDE OF BUILDING 32. NOTE: THESE RELOCATABLE TRAILERS ARE REQUIRED TO HAVE AN AUTOMATICE FIRE EXTINQUISHING SYSTEM INSTALLED THROUGHOUT AND ATTACHED TO THE BUILDING #32 SPRINKLER SYSTEM. THE SPRINKLERS ARE BEING USED FOR ALLOWABLE AREA INCREASE. ALL FIRE SPRINKLER WORK PER THE APPROVED PLANS AND ATTACHED COMMENT LIST. INSTALLATION SHALL CONFORM TO ADOPTED NFPA 13 1996 EDITION, BCO AND FIRE DEPARTMENT REQUIREMENTS. BLD00-01834 *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled11/28/200111/28/200111/28/2001PPASS
DetailsRick Jackson
Finaled by inspector at 11/28/2001 2:17:25 PM
Issue and Print Permit  4/2/2001 DONE
INSP-Final Inspection8/3/20008/3/20008/3/2000PPASS
DetailsRick Jackson
Added by Inspector: 409 On 8/3/2000
Inspection Record Card- Bld8/1/20008/1/20008/1/2000 DONE
Telephone call  8/1/2000 DONE
jerry ###-####
Sprinkler Plan Check7/28/2000 7/31/2000 PASS
DetailsBill Alexander
3 Copies received 07/28/2000.
Telephone call  7/31/2000 DONE
Plan review notes faxed to 2 fax numbers availabele for Jerry O'Niel (###-#### & ###-####.
Miscellaneous action  7/31/2000 DONE
Plan ands review notes taken to the front desk for calling, fee collection and permit release.
Meeting  7/25/2000 DONE
DetailsBill Alexander
JERRY O'NEIL - WENT OVER THE THIRD SUBMITTAL AND REVIEWED THE SAME PLANS AND CONTINUING PROBLEMS. SHOWED HIM THE PROBLEMS WITH HIS CALCULATING PROGRAM (DOES NOT SHOW TYPE OF FITTINGS IN FRICTION LOSS). DOES NOT SHOW FINAL RESULTS OTHER THAN A SIMPLE STARTING PRESSURE AND FLOW IN A GRAPH. PROVIDED A CALCULATION PROGRAM TO CHECK OUT AND INSTRUCTED THE DIFFERENCES WHICH ARE REQUIRED. Gave all plans and submittals back.
Sprinkler Plan Check7/25/2000 7/25/2000 FAIL
DetailsBill Alexander
PLANS DO NOT MEET MINIMUM REQUIREMENTS OR CORRELATE WITH CALCULATIONS.
Telephone call  7/24/2000 DONE
DetailsBill Alexander
TALKED TO JERRY O'NEIL CONCERNING SUBBMITTED PLANS AND FAILURES. HE INDICATED HE DID NOT RECEIVE FAXED REVIEW.
Telephone call  7/24/2000 DONE
DetailsBill Alexander
RE-FAXED REVIEW TO: ###-####AND NOT ###-#### (A SECOND AVAILABLE FAX)
Sprinkler Plan Check6/23/2000 6/23/2000 FAIL
DetailsBill Alexander
PLANS DO NO MEET MINIMUM REQUIREMENTS OR CORRELATE WITH CALCULATIONS. (No Change whatsoever?) SAME REVIEW APPLIES!
Sprinkler Plan Check6/13/2000 6/21/2000 FAIL
DetailsBill Alexander
PLANS DO NOT MEET MINIMUM REQUIREMENTS OR CORRELATE WITH CALCULATIONS.
Telephone call  6/21/2000 DONE
FAXED COPY OF FAILED REVIEW AND REQUIREMENTS TO JERRY O'NEIL @ ###-####.
Application received  6/13/2000 PASS
DetailsBill Alexander