Permit Information
Permit NumberFIR00-00513
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3800 E GRAND FOREST DR
Project NameSPR COLUMBIA VIL. LDS
Customer Number 
ePlanReview 
Description
COLUMBIA VILLAGE LDS CHURCH * TO FIRE SPRINKLER A 24,119 SQUARE FOOT TYPE III-1HR, FULLY FIRE SPRINKLERED SINGLE STORY ASSEMBLY BUILDING. EXTERIOR WALLS ARE MASONRY WITH INTERIOR FRAMING OF ONE-HOUR WOOD CONSTRUCTION. ALL PER APPROVED PLANS AND ATTACHMENTS. UNDERGROUND FIRE LINE PERMIT IS: FIR00-00318, BUILDING PERMIT IS: BLD00-03673, CUP99-0005. A FIRE ALARM SYSTEM IS REQUIRED FOR THIS BUILDING AND SPRINKLERS ARE USED FOR AREA INCREASE. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/14/20018/14/20018/14/2001PPASS
DetailsRick Jackson
Added by Inspector: 409 On 8/14/2001 4:30:26 PM
DOC - Permit Finaled8/14/20018/14/20018/14/2001PPASS
DetailsRick Jackson
Finaled by inspector at 8/14/2001 4:31:44 PM
INSP-Final Inspection3/27/20013/30/20013/30/2001APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 03/27/2001 at 16:46:32. Contact: ###-####.
INSP-Supply line flush2/23/20012/23/20012/23/2001PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 02/23/2001 at 08:22:23. Contact: ###-####. hydro test okay on underground 2/23/2001 10:50:11 AM
INSP-Sprinkler Rough-in/Hydro2/21/20012/21/20012/21/2001PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 02/21/2001 at 09:32:15. Contact: ###-####. hydro test okay for overhead of both dry and wet systems; still need to hydro the underground 2/21/2001 5:27:17 PM
Issue permit  2/20/2001 DONE
Inspection Record Card- Bld1/12/20011/12/20011/12/2001 DONE
Sprinkler Plan Check1/11/2001 1/11/2001 DONE
DetailsBill Alexander
Resubmittal - Complete Set - Attic Modifications.
PLANS/APPL TAKEN TO FRONT DESK  1/11/2001 DONE
DetailsBill Alexander
Plan assigned to (Bill)9/1/2000 1/11/2001 DONE
DetailsBill Alexander
1/11/2001 15:40:03 JWA - activity updated through activity FIRA22 from case FIR00-00513.
Sprinkler Plan Check12/15/2000 1/9/2001 FAIL
DetailsBill Alexander
Dry system piping does not meet NFPA 13. Other remote area requires calculations. Drain and Inspectors test is not to NFPA 13.
Telephone call  1/9/2001 DONE
Called Don Weland and went over plans and continuing problems in review. Required resubmittal of the Dry System.
INSP-Sprinkler Rough-in12/6/200012/6/200012/6/2000PFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/6/2000 4:00:51 PM ///// heads overspaced in cathedral area; sprinklers required under stage; dry plans not on-site; insulation covering wet pipe 12/6/2000 4:03:13 PM
INSP-Supply line flush12/4/200012/5/200012/6/2000APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/04/2000 at 15:40:04. Contact: ###-####.////flush already complete 12/6/2000 4:01:36 PM
INSP-Supply line flush12/1/200012/4/200012/4/2000PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/01/2000 at 11:43:32. Contact: ###-####.////// underground flush okay 12/4/2000 3:10:25 PM
Sprinkler Plan Check11/22/2000 12/2/2000 FAIL
DetailsBill Alexander
2nd submittal - Lack complete readable plans and previous followup plans. Provided (5/12 pitch), 12/15/2000. Revised attic plans completely!
Telephone call  12/1/2000 DONE
Faxed copy of failed review to Shilo Auto. Spr. Co.
Issue permit  9/21/2000 DONE
Inspection Record Card- Bld9/19/20009/19/20009/19/2000 DONE
Telephone call  9/19/2000 DONE
called permit ready
Sprinkler Plan Check9/1/2000 9/19/2000 PASS
DetailsBill Alexander
PARTIAL APPROVAL TO PRECEED WITH RESUBMITTAL OF:
Plans are of a quality that will require resubmittal for clarity in archive scanning City of Boise records. provide completed plans that include all node points on the riser details. Provide in your section on the Attic Sprinkler Piping and head location (plan 5 of 5) minimum & maximum distances allowed from the Peak. Provide the pitch of the roof system on plan 5 of 5, to verify SD1 listed limitations.
Provide a note on the plans that the dry system piping shall be pitched to meet the minimum pitched per NFPA 13:4-14.3.3.
Sprinkler Plan Check9/1/2000 9/19/2000 PASS
DetailsBill Alexander
PARTIAL * Passed on condition that new readable plans be submitted. Dry system failed due to complete information. Resubmittal required.
Application received  9/1/2000  
Case Summary    DONE