Permit Information
Permit NumberFIR00-00548
StatusFinaled
Name GRINNELL FIRE PROTECTION
Site Address 6051 N EAGLE
Project NameSPR EAGLE MED BLDG. #2
Customer Number 
ePlanReview 
Description
EAGLE MEDICAL CENTER BUILDING #2 * TO FIRE SPRINKLER THE BASEMENT OF A TYPE VN, B/31, SINGLE STORY, 3,116 SQ.FT. MEDICAL OFFICE BUILDING WITH A 1,340 SQ.FT. BASEMENT, NOTE: THIS BASEMENT IS FULLY FIRE SPRINKLERED FOR BASEMENT SEPARATION. ALL FIRE SPRINKLER WORK PER THE APPROVED PLANS, ATTACHED COMMENT LIST. THE FOOTING/FOUNDATION PERMIT IS: BLD00-00120. THE GRADING PERMIT IS: BLD00-00159. THE BUILDING PERMIT IS: BLD00-01574. DRH99-00197 *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20019/19/20019/19/2001PPASS
DetailsJoe Tawney
Added by Inspector: 406 On 9/19/2001 1:01:30 PM
DOC - Permit Finaled9/19/20019/19/20019/19/2001PPASS
DetailsJoe Tawney
Finaled by inspector at 9/19/2001 1:01:34 PM
INSP-Final Inspection12/29/20001/2/20011/2/2001PCANC
DetailsJoe Tawney
###-#### Cancel No spklr required per change to permit BLD00-01574 1/3/2001 8:29:11 AM
INSP-Final Inspection12/21/200012/21/200012/21/2000PFAIL
DetailsJoe Tawney
Final Fail C/N issued 12/29/2000 2:08:59 PM
Issue permit  10/16/2000 DONE
Inspection Record Card- Bld10/2/200010/2/200010/2/2000 DONE
Telephone call  10/2/2000 DONE
###-####
Sprinkler Plan Check9/29/2000 9/29/2000 PASS
DetailsBill Alexander
Telephone call  9/29/2000 DONE
Copy of review notes faxed to Grinnell
PLANS/APPL TAKEN TO FRONT DESK  9/29/2000 DONE
DetailsBill Alexander
Telephone call  9/25/2000 DONE
Copy of failed review faxed to Grinnell.
Sprinkler Plan Check9/21/2000 9/22/2000 FAIL
DetailsBill Alexander
Not meeting minimum design requirements for construction use. Wrong material listing use.
Plan assigned to (Bill)9/8/2000 9/20/2000 PASS
DetailsBill Alexander
Sprinkler Plan Check9/8/2000 9/20/2000 FAIL
DetailsBill Alexander
A. Calculations lacked fire sprinkler cover sheet.
B. Water supply certification is lacking.
C. Legend does not indicate whether the sprinkler is a pendant or upright since the type is not filled out. Provide head submittal data.
D. Provide Backflow manufacturer, make and model/s. NFPA 13:6-1.1.1 (oo)
E. Floor plan does not show room identifications and dimensions. NFPA 13:6-1.1.1 (g)
F. Each (final) Remote Area calculated shall be provided with the information of: Density/sq. ft., BOR demand in gpm @ psi, w/ number of heads, as a MINIMUM. NFPA 13:6-1.1.1 (ee)
G. Provide type and location of joints (fittings indicated in the calculation connection to different pipe types on the system 4" main. NFPA 13:6-1.1.1 (u)
H. Provide connecting fitting information on underground supply and overhead piping. What is steel and what is CPVC or other? What is concealed and what is exposed, etc. NFPA 13:6-1.1.1 (u)
I. Provide size of city main in the street and whether it is dead-end or circulating. NFPA 13:6-1.1.1 (j)
J. Provide nearest fire hydrant on site plan.
Telephone call  9/20/2000 DONE
COPY OF FAILED REVIEW FAXED TO GRINNELL.
Application received  9/8/2000 PASS
DetailsBill Alexander
Case Summary    DONE