INSP-Final Inspection | 9/19/2001 | 9/19/2001 | 9/19/2001 | P | PASS |
Joe Tawney
|
|
|
Added by Inspector: 406 On 9/19/2001 1:01:30 PM
|
DOC - Permit Finaled | 9/19/2001 | 9/19/2001 | 9/19/2001 | P | PASS |
Joe Tawney
|
|
|
Finaled by inspector at 9/19/2001 1:01:34 PM
|
INSP-Final Inspection | 12/29/2000 | 1/2/2001 | 1/2/2001 | P | CANC |
Joe Tawney
|
|
|
###-#### Cancel No spklr required per change to permit BLD00-01574 1/3/2001 8:29:11 AM
|
INSP-Final Inspection | 12/21/2000 | 12/21/2000 | 12/21/2000 | P | FAIL |
Joe Tawney
|
|
|
Final Fail C/N issued 12/29/2000 2:08:59 PM
|
Issue permit | | | 10/16/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 10/2/2000 | 10/2/2000 | 10/2/2000 | | DONE |
|
|
|
|
Telephone call | | | 10/2/2000 | | DONE |
|
|
|
###-####
|
Sprinkler Plan Check | 9/29/2000 | | 9/29/2000 | | PASS |
Bill Alexander
|
|
|
|
Telephone call | | | 9/29/2000 | | DONE |
|
|
|
Copy of review notes faxed to Grinnell
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/29/2000 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 9/25/2000 | | DONE |
|
|
|
Copy of failed review faxed to Grinnell.
|
Sprinkler Plan Check | 9/21/2000 | | 9/22/2000 | | FAIL |
Bill Alexander
|
|
|
Not meeting minimum design requirements for construction use. Wrong material listing use.
|
Plan assigned to (Bill) | 9/8/2000 | | 9/20/2000 | | PASS |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 9/8/2000 | | 9/20/2000 | | FAIL |
Bill Alexander
|
|
|
A. Calculations lacked fire sprinkler cover sheet.
B. Water supply certification is lacking.
C. Legend does not indicate whether the sprinkler is a pendant or upright since the type is not filled out. Provide head submittal data.
D. Provide Backflow manufacturer, make and model/s. NFPA 13:6-1.1.1 (oo)
E. Floor plan does not show room identifications and dimensions. NFPA 13:6-1.1.1 (g)
F. Each (final) Remote Area calculated shall be provided with the information of: Density/sq. ft., BOR demand in gpm @ psi, w/ number of heads, as a MINIMUM. NFPA 13:6-1.1.1 (ee)
G. Provide type and location of joints (fittings indicated in the calculation connection to different pipe types on the system 4" main. NFPA 13:6-1.1.1 (u)
H. Provide connecting fitting information on underground supply and overhead piping. What is steel and what is CPVC or other? What is concealed and what is exposed, etc. NFPA 13:6-1.1.1 (u)
I. Provide size of city main in the street and whether it is dead-end or circulating. NFPA 13:6-1.1.1 (j)
J. Provide nearest fire hydrant on site plan.
|
Telephone call | | | 9/20/2000 | | DONE |
|
|
|
COPY OF FAILED REVIEW FAXED TO GRINNELL.
|
Application received | | | 9/8/2000 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|