INSP-Final Inspection | 2/19/2002 | 2/20/2002 | 2/20/2002 | P | PASS |
Rick Jackson
|
|
|
###-#### MELISSA
|
DOC - Permit Finaled | 2/20/2002 | 2/20/2002 | 2/20/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/20/2002 4:18:56 PM
|
INSP-Alarm Testing | 1/2/2002 | 1/4/2002 | 1/4/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/02/2002 at 13:27:03. Contact: . attempted test of 24E systems; preaction okay; started testing smoke/fire dampers and two didn't operate with associated detector - tested will be rescheduled when they are pretested properly 1/4/2002 10:14:19 AM
|
INSP-Alarm Testing | 11/13/2001 | 11/10/2001 | 11/10/2001 | A | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/13/2001 7:11:17 AM completed all alarm testing and sprinkler monitoring for building 24D only; okay to occupy bldg 24D only
|
INSP-Alarm Testing | 11/13/2001 | 11/9/2001 | 11/9/2001 | A | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/13/2001 7:13:29 AM couldn't complete testing not enough time
|
INSP-Sprinkler Rough-in/Hydro | 11/9/2001 | 11/9/2001 | 11/9/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 11/9/2001 6:11:32 AM wrong category of inspection; alarm testing 11/13/2001 7:12:06 AM
|
INSP-Alarm Testing | 11/7/2001 | 11/8/2001 | 11/8/2001 | A | FAIL |
Rick Jackson
|
|
|
not ready for testing 11/13/2001 7:09:52 AM
|
FIR-Aging Inspection | 8/20/2001 | 8/20/2001 | 8/20/2001 | | NR |
Rick Jackson
|
|
|
work still in progress 8/20/2001 9:55:56 AM
|
Issue and Print Permit | | | 5/21/2001 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/18/2001 | | PASS |
|
|
|
Final revision of comments per telcon with Micron yesterday.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/18/2001 | | PASS |
|
|
|
|
Inspection Record Card- Fire | 5/18/2001 | | 5/18/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/18/2001 | | DONE |
|
|
|
emailed permit ready
|
Alarm Plan Check | | | 4/7/2001 | | HOLD |
|
|
|
3rd review - HOLD - Holding plans subject to confirmation from Micron that these plans are acceptable to them, since submittal came directly from designer, ap-arnently bypassing Micron. Paul Marcolina to investigate and advise disposition.
Reconfirmed same pending status with Paul as of 4/27.
|
Plan assigned to (SAM) | 9/28/2000 | | 3/5/2001 | | DONE |
|
|
|
3/5/2001 14:51:07 JWA - activity updated through activity FIRA22 from case FIR01-00076.
|
Alarm Plan Check | 10/25/2000 | | 1/2/2001 | | FAIL |
|
|
|
Lack full sheet/information of complete system and NFPA 72 issues.
|
Telephone call | | | 1/2/2001 | | DONE |
|
|
|
Faxed copy of failed review to HDR.
|
Alarm Plan Check | | | 10/13/2000 | | FAIL |
|
|
|
12/20/00 Fed exed fire alarm plans and documents to Floyd. KMM comments faxed to HDR and Micron 10/13
|
Application received | | | 9/28/2000 | | |
|
|
|
|