DOC - Permit Finaled | 1/10/2002 | 1/10/2002 | 1/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/10/2002 4:04:08 PM
|
INSP-Final Inspection | 1/11/2001 | 1/11/2001 | 1/11/2001 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/11/2001 at 09:12:19. Contact: ###-####.
|
INSP-Final Inspection | 1/2/2001 | 1/4/2001 | 1/4/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 1/2/2001 10:05:25 AM 1:00 pm------ spare heads; outside control valve; BFP springs require repair kit 1/4/2001 1:44:38 PM
|
INSP-Final Inspection | 12/27/2000 | 1/2/2001 | 1/2/2001 | A | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/27/2000 at 11:48:58. Contact: ###-####.
|
INSP-Supply line flush | 12/11/2000 | 12/12/2000 | 12/12/2000 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/11/2000 at 16:20:55. Contact: ###-####./// supply line flush okay 12/12/2000 3:32:15 PM
|
INSP-Supply line flush | 11/3/2000 | 11/6/2000 | 11/6/2000 | A | CANC |
Rick Jackson
|
|
|
Jason ###-####--cancel per david
|
Issue and Print Permit | | | 11/3/2000 | | DONE |
|
|
|
|
Issue permit | | | 11/3/2000 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2000 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Bld | 11/2/2000 | 11/2/2000 | 11/2/2000 | | DONE |
|
|
|
|
Telephone call | | | 11/2/2000 | | DONE |
|
|
|
talked to Dave Barns ###-#### w/commercial fire protection
|
Telephone call | | | 11/2/2000 | | DONE |
|
|
|
Faxed copy a passed review to Commercial Fire
|
Plan assigned to (Bill) | 10/20/2000 | | 11/2/2000 | | DONE |
|
|
|
11/2/2000 13:42:09 JWA - activity updated through activity FIRA22 from case FIR00-00598.
|
Sprinkler Plan Check | 11/1/2000 | | 11/2/2000 | | PASS |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 10/23/2000 | | 10/30/2000 | | FAIL |
Bill Alexander
|
|
|
Building does not conform to UFC Article 81 as designed.
|
Telephone call | | | 10/30/2000 | | DONE |
|
|
|
Faxed failed review to Commercial Fire.
|
Application received | | | 10/20/2000 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|