DOC - Permit Finaled | 5/14/2001 | 5/14/2001 | 5/14/2001 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/14/2001 3:30:15 PM
|
INSP-Final Inspection | 5/14/2001 | 5/14/2001 | 5/14/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 5/14/2001 3:29:48 PM
|
INSP-Final Inspection | 5/4/2001 | 5/7/2001 | 5/7/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/04/2001 at 09:40:50. Contact: ###-####. dry system test at 59 seconds; need to test alarms 5/7/2001 11:13:13 AM
|
INSP-Final Inspection | 5/3/2001 | 5/3/2001 | 5/3/2001 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/03/2001 at 08:41:54. Contact: ###-####. okay on aerosol racking 5/3/2001 2:49:07 PM
|
INSP-Final Inspection | 4/26/2001 | 4/27/2001 | 4/27/2001 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/26/2001 at 12:38:05. Contact: ###-####.
|
INSP-Final Inspection | 4/9/2001 | 4/11/2001 | 4/11/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/09/2001 at 15:26:19. Contact: ###-####. dry sprinkler system took 72 seconds; inspector test in wrong location 4/11/2001 6:12:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/14/2001 at 15:22:22. Contact: ###-####. hydro on all wet systems okay 3/15/2001 1:16:21 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2001 | 3/14/2001 | 3/14/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/13/2001 at 08:31:16. Contact: ###-####. c/n issued 3/14/2001 11:33:06 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/19/2001 | 2/20/2001 | 2/20/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 02/19/2001 at 08:30:50. Contact: ###-####. c/n issued - earthquaking; FDC location; clearance at base of riser; dry and rack systems not approved 2/21/2001 10:33:44 AM
|
Sprinkler Plan Check | 2/1/2001 | | 2/15/2001 | | PASS |
Bill Alexander
|
|
|
Required racking revisions and dry system response.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/15/2001 | | DONE |
Bill Alexander
|
|
|
Required revised racking changes and verifications. Including additonal review notes added.
|
Telephone call | | | 2/15/2001 | | DONE |
Bill Alexander
|
|
|
Faxed copy of review to Shilo.
|
Issue permit | | | 2/15/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 1/8/2001 | 1/8/2001 | 1/8/2001 | | DONE |
|
|
|
|
Telephone call | | | 1/8/2001 | | DONE |
|
|
|
called permit ready
|
Issue and Print Permit | | | 1/8/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/14/2000 | | 1/5/2001 | | DONE |
|
|
|
1/5/2001 09:42:53 JWA - activity updated through activity FIRA22 from case FIR00-00627.
|
Sprinkler Plan Check | 12/15/2000 | | 1/5/2001 | | PASS |
Bill Alexander
|
|
|
Partial! Need resubmittal of the Dry system, aerosols racking and combustible liquids racking!
|
Telephone call | | | 1/5/2001 | | DONE |
|
|
|
Copy of review faxed to Shilo and TVA.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/5/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 11/29/2000 | | DONE |
Bill Alexander
|
|
|
Copy of failed review notes faxed to Shilo Fire Protection.
|
Sprinkler Plan Check | 11/14/2000 | | 11/29/2000 | | FAIL |
Bill Alexander
|
|
|
Water supply used is not certified by United Water. Some questions: Dry systrem exceeds maximum allowed by 1,350 gallons, lack data submittals on heads, compressor, and many other items. Need clarification of relating elevations, elevation changes, corelating floor to detail and section plans, etc. Aaresols calcs not working.
|
Application received | | | 11/14/2000 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|