Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR00-00630
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 1276 W RIVER ST
Project NameSPR RIVER PLAZA
Customer Number 
ePlanReview 
Description
TO FIRE SPRINKLER A NEW 3-STORY, WOOD FRAMED, TYPE V ONE-HOUR, 26,851 ft/2, SHELL AND CORE OFFICE BUILDING. THE FIRST FLOOR IS APPROXIMATELY 8,987 FT/2 THE SECOND FLOOR IS APPROXIMATELY 9,054 FT/2 THE THIRD FLOOR IS APPROXIMATELY 8,810 FT/2. THE INSTALLATION OF THE FIRE SPRINKLER SYSTEM IS USED TO SUBSTITUTE FOR THE ONE-HOUR FIRE-RESISTIVE CONSTRUCTION. ALL WORK PER THE APPROVED PLANS, ATTACHED COMMENT LIST, THE 1997 EDITION OF THE UFC, BOISE CITY ORDINANCE, FIRE DEPARTMENT APPROVAL AND INSTALLED PER RELATED ADOPTED PAMPHLETS. FOUNDATION PERMIT IS BLD99-2056. THIS PERMIT IS FOR THE SHELL ONLY. THE SECOND AND THIRD FLOORS MUST HAVE THE CORRIDOR FINISHED TO PROVIDE ACCESS TO THE SECOND MEANS OF REQUIRED EGRESS. THIS REQUIREMENT MUST BE FINISHED AT THE TIME OF THE FIRST OCCUPANT. UNDERGROUND FIRE LINE WAS PERMITTED UNDER FIR00-00025. BLD99-02394 (SHELL), FUTURE T.I.'S BLD00-02397 (3RD FLOOR) AND BLD00-02507 (2ND FLOOR), DRH99-0067. This permit is attached to the shell permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference8/14/20018/14/20018/14/2001PPASS
DetailsRick Jackson
Added by Inspector: 409 On 8/14/2001 4:12:44 PM
DOC - Permit Finaled8/14/20018/14/20018/14/2001PPASS
DetailsRick Jackson
Finaled by inspector at 8/14/2001 4:14:27 PM
INSP-Final Inspection1/9/20011/9/20011/9/2001APASS
DetailsRick Jackson
Scheduled by Inspector: 409 On 1/9/2001 8:57:26 AM
INSP-Final Inspection1/9/20011/8/20011/8/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 1/9/2001 9:00:09 AM dry air pressure not working; valve not supervised; check valve needs repair kit; standard response head in elevator machine room 1/9/2001 9:02:43 AM
INSP-Final Inspection12/29/200012/29/20001/2/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/29/2000 at 09:08:04. Contact: ###-####. outside control valve; hydro dry and FDC; tampers on dry system 1/2/2001 10:06:20 AM
INSP-Supply line flush12/27/200012/28/200012/28/2000ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/27/2000 at 11:45:08. Contact: ###-####.
INSP-Supply line flush12/26/200012/27/200012/27/2000APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/26/2000 at 13:40:07. Contact: ###-####./// flush okay 12/27/2000 4:17:09 PM
INSP-Supply line flush12/15/200012/15/200012/15/2000PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/15/2000 at 09:35:03. Contact: ###-####.///// underground hydro only okay 12/15/2000 4:04:47 PM
INSP-Sprinkler Rough-in/Hydro12/8/200012/11/200012/11/2000PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/08/2000 at 09:31:17. Contact: ###-####./// hydro okay on attic system. need additional sway bracing; overspaced heads; painted heads; inspectors test not installed per plans and will relocate 12/12/2000 9:41:21 AM
Telephone call  12/6/2000 DONE
talked to dave to verify plans are ready
Issue permit  12/6/2000 DONE
Inspection Record Card- Bld12/5/200012/5/200012/5/2000 DONE
Plan assigned to (Bill)11/15/2000 12/5/2000 DONE
12/5/2000 09:08:53 JWA - activity updated through activity FIRA22 from case FIR00-00630.
Sprinkler Plan Check12/4/2000 12/5/2000 PASS
DetailsBill Alexander
Telephone call  12/5/2000 DONE
Faxed copy of review to Commerical.
PLANS/APPL TAKEN TO FRONT DESK  12/5/2000 DONE
DetailsBill Alexander
Sprinkler Plan Check11/27/2000 12/4/2000 FAIL
DetailsBill Alexander
Calculation problem needs verified.
Telephone call  12/4/2000 FAIL
DetailsBill Alexander
Phoned John Warnick 2:00pm on dry system calc elevations not jiving with structure, in which case it would appear the elevation plugged in to low for the attic head locations.
Telephone call  11/16/2000 DONE
DetailsBill Alexander
Copy of failed review faxed to Commercial.
Sprinkler Plan Check11/3/2000 11/16/2000 FAIL
DetailsBill Alexander
Need hanger locations, dimensioned elevation to verifiy calculation elevation pressure losses, clarification of room identifications of tenants, clarrification of construction (NFPA 13:1-4.6), sprinkler head data submittals, copy of the underground supply attached to these plans for calculation verification, (done under a seperated permit), pendants not shown in this permit, capacity of dry system......etc.
Application received  11/3/2000 PASS
DetailsBill Alexander
Case Summary    DONE