INSP-Final Inspection | 9/13/2001 | 9/14/2001 | 9/14/2001 | A | PASS |
Joe Tawney
|
|
|
Reinsp OK on spklr system and alarms 9/13/2001 11:47:05 AM
|
DOC - Permit Finaled | 9/13/2001 | 9/13/2001 | 9/13/2001 | P | PASS |
Joe Tawney
|
|
|
Finaled by inspector at 9/13/2001 11:47:11 AM
|
INSP-Final Inspection | 9/7/2001 | 9/10/2001 | 9/10/2001 | P | NR |
Joe Tawney
|
|
|
Not ready to be rescheduled 9/10/2001 11:08:35 AM
|
INSP-Final Inspection | 8/9/2001 | 8/9/2001 | 8/9/2001 | P | FAIL |
Joe Tawney
|
|
|
Final Fail Alarm system failed 8/9/2001 3:49:29 PM
|
Sprinkler Plan Check | 1/9/2001 | | 1/18/2001 | | PASS |
|
|
|
Plans are resubmittals for cleanup attachments to originals.
|
INSP-Final Inspection | 1/8/2001 | 1/9/2001 | 1/9/2001 | A | PART |
Joe Tawney
|
|
|
Ann ###-#### Rough in Relocate 2 heads. coverage under stairs. OK to cover. 1/9/2001 12:50:31 PM
|
Inspection Record Card- Bld | 1/8/2001 | 1/8/2001 | 1/8/2001 | | DONE |
|
|
|
|
Telephone call | | | 1/8/2001 | | DONE |
|
|
|
talked to shelly to verify plans are ready
|
Sprinkler Plan Check | 1/8/2001 | | 1/8/2001 | | FAIL |
Bill Alexander
|
|
|
*RECALCULATIONS* DO NOT WORK FOR THE MAIN AND UPPER FLOORS! New spacing requirements needed. Wrote letter of resubmittal requirements.
|
Telephone call | | | 1/8/2001 | | DONE |
|
|
|
Faxed copy of review letter and requirements to Shilo. Calculations do not meet minimum code.
|
Issue permit | | | 1/8/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/22/2000 | | 1/5/2001 | | DONE |
|
|
|
1/5/2001 17:08:19 JWA - activity updated through activity FIRA22 from case FIR00-00643.
|
Sprinkler Plan Check | 1/5/2001 | | 1/5/2001 | | PASS |
Bill Alexander
|
|
|
Partial - Need recacluations meeting minimum listed sprinkler density/pressures.
|
Telephone call | | | 1/5/2001 | | DONE |
|
|
|
faxed copy of review to Shilo
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/5/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 12/15/2000 | | 12/21/2000 | | FAIL |
Bill Alexander
|
|
|
Elevation does not match plans with calcs. Underground calculated piping does not match plans. Garage and living space is not protected with living space over garage. Need to verify elevation from meter to base of riser.
|
Telephone call | | | 12/21/2000 | | DONE |
Bill Alexander
|
|
|
Called James Thomas and went through the plans step by step to show problems.
|
Sprinkler Plan Check | 12/22/2000 | | 12/1/2000 | | FAIL |
Bill Alexander
|
|
|
plan quality is so poor they are rejected.
|
Telephone call | | | 12/1/2000 | | DONE |
|
|
|
Copy of failed review faxed to Shilo Fire Protection.
|
Application received | | | 11/22/2000 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|