Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR00-00643
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5527 N QUAIL SUMMIT PL
Project NameSPR HILLSIDE HOME
Customer Number 
ePlanReview 
Description
To fire sprinkler a 2337 ft/2 two story single family dwelling with a 1726 ft/2 unfinished basement, (facility has two attached garages, 922 ft/2 four car at north side of structure, 288 ft/2 one car at south side), per approved plans, all engineering/red-lining and attached requirement lists. (1st floor 1798 ft/2, 2nd floor 539 ft/2. This lot is within a hillside area and is subject to the hillside ordinances. Class "A" roof system to be installed. This lot shall be fitted with an NFPA 13D "Modified" fire sprinkler system including attached garages. The sprinkler flow alarm shall be attached to the residence smoke detection system per NFPA 72:2-2.1.1.3. Note: Separate permits will be required to finish basement area. BLD00-01086, PC #412 CU #94-90. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/13/20019/14/20019/14/2001APASS
DetailsJoe Tawney
Reinsp OK on spklr system and alarms 9/13/2001 11:47:05 AM
DOC - Permit Finaled9/13/20019/13/20019/13/2001PPASS
DetailsJoe Tawney
Finaled by inspector at 9/13/2001 11:47:11 AM
INSP-Final Inspection9/7/20019/10/20019/10/2001PNR
DetailsJoe Tawney
Not ready to be rescheduled 9/10/2001 11:08:35 AM
INSP-Final Inspection8/9/20018/9/20018/9/2001PFAIL
DetailsJoe Tawney
Final Fail Alarm system failed 8/9/2001 3:49:29 PM
Sprinkler Plan Check1/9/2001 1/18/2001 PASS
Plans are resubmittals for cleanup attachments to originals.
INSP-Final Inspection1/8/20011/9/20011/9/2001APART
DetailsJoe Tawney
Ann ###-#### Rough in Relocate 2 heads. coverage under stairs. OK to cover. 1/9/2001 12:50:31 PM
Inspection Record Card- Bld1/8/20011/8/20011/8/2001 DONE
Telephone call  1/8/2001 DONE
talked to shelly to verify plans are ready
Sprinkler Plan Check1/8/2001 1/8/2001 FAIL
DetailsBill Alexander
*RECALCULATIONS* DO NOT WORK FOR THE MAIN AND UPPER FLOORS! New spacing requirements needed. Wrote letter of resubmittal requirements.
Telephone call  1/8/2001 DONE
Faxed copy of review letter and requirements to Shilo. Calculations do not meet minimum code.
Issue permit  1/8/2001 DONE
Plan assigned to (Bill)11/22/2000 1/5/2001 DONE
1/5/2001 17:08:19 JWA - activity updated through activity FIRA22 from case FIR00-00643.
Sprinkler Plan Check1/5/2001 1/5/2001 PASS
DetailsBill Alexander
Partial - Need recacluations meeting minimum listed sprinkler density/pressures.
Telephone call  1/5/2001 DONE
faxed copy of review to Shilo
PLANS/APPL TAKEN TO FRONT DESK  1/5/2001 DONE
DetailsBill Alexander
Sprinkler Plan Check12/15/2000 12/21/2000 FAIL
DetailsBill Alexander
Elevation does not match plans with calcs. Underground calculated piping does not match plans. Garage and living space is not protected with living space over garage. Need to verify elevation from meter to base of riser.
Telephone call  12/21/2000 DONE
DetailsBill Alexander
Called James Thomas and went through the plans step by step to show problems.
Sprinkler Plan Check12/22/2000 12/1/2000 FAIL
DetailsBill Alexander
plan quality is so poor they are rejected.
Telephone call  12/1/2000 DONE
Copy of failed review faxed to Shilo Fire Protection.
Application received  11/22/2000 PASS
DetailsBill Alexander
Case Summary    DONE