Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR00-00705
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 8174 W RIFLEMAN ST
Project NameSPR SEATTLE LIGHTING
Customer Number 
ePlanReview 
Description
SEATTLE LIGHTING * TO FIRE SPRINKLER A NEW SINGLE STORY, 12,200 FT/2 RETAIL SHOWROOM AND WAREHOUSE BUILDING. THE RETAIL AREA IS APPROXIMATELY 7,7,00 FT/2 AND THE WAREHOUSE AREA IS 4,300 FT/2 NOTE: THIS BUILDING IS REQUIRED TO BE FULLY FIRE SPRINKLERED FOR AREA INCREASE. ALL FIRE SPRINKLER WORK PER THE APPROVED PLANS, ATTACHED COMMENT LIST , UFC, ADOPTED NFPA PAMPHLETS, BCO'S AND FIRE DEPARTMENT APPROVAL. SCOPE OF WORK INCLUDES ALL SITE IMPROVEMENTS. UNDERGROUND INSTALLED UNDER FIR00-00614. BUILDING PERMIT IS: BLD00-01979. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro4/26/20014/26/20014/26/2001PPASS
DetailsJoe Tawney
above ground hydro test becky ###-#### OK on spklr rough in 4/26/2001 5:48:05 PM
INSP-Final Inspection4/26/20014/26/20014/26/2001PNR
DetailsJoe Tawney
becky ###-#### Not ready for inspection 4/26/2001 5:48:45 PM
INSP-Sprinkler Rough-in/Hydro4/16/20014/17/20014/17/2001PFAIL
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 04/16/2001 at 17:05:19. Contact: ###-####. Fail Spklr rough in. 4/17/2001 3:07:32 PM
INSP-Final Inspection4/16/20014/17/20014/17/2001PNR
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 04/16/2001 at 17:05:57. Contact: ###-####.
INSP-Sprinkler Rough-in/Hydro4/17/20014/17/20014/17/2001PPASS
DetailsJoe Tawney
Added by Inspector: 406 On 4/17/2001 3:08:36 PM OK on above ground hydro test
Issue and Print Permit  4/16/2001 DONE
Sprinkler Plan Check4/13/2001 4/13/2001 PASS
REsubmittal approved on RUSH basis.
PLANS/APPL TAKEN TO FRONT DESK  4/13/2001 PASS
Inspection Record Card- Fire4/13/2001 4/13/2001 DONE
Telephone call  4/13/2001 DONE
called permit ready
Miscellaneous action  4/12/2001  
Refaxed review to contractor. Review of 1/10/01 was inadvertently addressed & faxed to Grinnell instead of DeBest
Plan assigned to (Bill)12/28/2000 1/30/2001 DONE
1/30/2001 11:50:17 SLR - activity updated through activity FIRA22 from case FIR00-00703.
Telephone call  1/10/2001 DONE
DetailsBill Alexander
COPY OF FAILED REVIEW FAXED TO DEBEST
Sprinkler Plan Check12/28/2000 1/10/2001 FAIL
DetailsBill Alexander
lack outside control, risers clacs and connections seem to not match. Rooms are not idenitifed.
Application received  12/28/2000 PASS
DetailsBill Alexander