INSP-Final Inspection | 11/19/2001 | 11/20/2001 | 11/20/2001 | A | PASS |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 11/19/2001 5:24:18 PM
|
DOC - Permit Finaled | 11/20/2001 | 11/20/2001 | 11/20/2001 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/20/2001 7:10:48 PM
|
INSP-Final Inspection | 11/16/2001 | 11/19/2001 | 11/19/2001 | P | FAIL |
Rick Jackson
|
|
|
###-#### DAVE X2 bell shut-off problems; preaction not ready 11/19/2001 5:23:55 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/1/2001 | 11/2/2001 | 11/2/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/01/2001 at 09:51:53. Contact: ###-####. hydro on cafeteria only okay. 11/2/2001 9:59:32 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/26/2001 | 10/29/2001 | 10/29/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/26/2001 at 12:01:05. Contact: ###-####. fireproofing on heads; EQ'ing not completed; need hydro test still 10/29/2001 3:00:50 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2001 | 10/26/2001 | 10/26/2001 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/25/2001 at 08:52:14. Contact: ###-####. received a call from Mike and they will reschedule for 10/29 10/26/2001 11:55:17 AM
|
FIR-Aging Inspection | 6/19/2001 | 6/19/2001 | 6/19/2001 | | NR |
Rick Jackson
|
|
|
work still under progress 6/19/2001 10:37:31 AM
|
Issue and Print Permit | | | 3/20/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 3/1/2001 | 3/1/2001 | 3/1/2001 | | DONE |
|
|
|
|
Telephone call | | | 3/1/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/10/2001 | | 3/1/2001 | | DONE |
|
|
|
3/1/2001 15:53:35 JWA - activity updated through activity FIRA22 from case FIR01-00010.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/20/2001 | | 2/26/2001 | | DONE |
Bill Alexander
|
|
|
Submittal #2 (a resubmittal). Still some apparant overspacing, which were noted, redlined and must be verified by the field inspector.
|
Telephone call | | | 2/26/2001 | | DONE |
|
|
|
Faxed copy of review to Shilo.
|
Telephone call | | | 1/24/2001 | | DONE |
Bill Alexander
|
|
|
Called Shawn Fenneran of failed review and asked for meeting due to large list of problems (also associated with FIR01-00011).
|
Sprinkler Plan Check | 1/10/2000 | | 1/23/2001 | | FAIL |
Bill Alexander
|
|
|
FIR01-00010 and FIR01-00011 submitted together. Fire Code problems with design spacing, etc.
|
Application received | | | 1/10/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|