DOC - Permit Finaled | 11/20/2001 | 11/20/2001 | 11/20/2001 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/20/2001 7:28:35 PM
|
INSP-Final Inspection | 11/20/2001 | 11/20/2001 | 11/20/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/20/2001 7:28:23 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/12/2001 | 10/15/2001 | 10/15/2001 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/12/2001 at 11:07:36. Contact: ###-####. pre-action hydro okay; all items from previous inspection corrected; areas 1-2 (cafeteria) not completed. 10/15/2001 2:27:11 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/3/2001 | 10/4/2001 | 10/4/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/03/2001 at 15:26:21. Contact: ###-####. hydro on all systems except 1-2 and preaction completed; need EQ on basement main 10/4/2001 3:39:11 PM
|
INSP-Sprinkler Rough-in | 9/24/2001 | 9/25/2001 | 9/25/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 9/24/2001 2:50:52 PM around 10 am EQ's see FP sheets for areas 3-4-5-6 on first floor 9/25/2001 11:34:22 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/21/2001 | 9/24/2001 | 9/24/2001 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 09/21/2001 at 09:05:22. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 9/19/2001 | 9/21/2001 | 9/21/2001 | A | CANC |
Joe Tawney
|
|
|
Cancel To be rescheduled to 9/24/01 9/21/2001 9:08:40 AM
|
INSP-Sprinkler Rough-in | 9/13/2001 | 9/14/2001 | 9/14/2001 | A | FAIL |
Rick Jackson
|
|
|
r/i- forest- ###-#### need EQ between area5-6 on 2nd floor; need EQ at stair in area 4. 9/14/2001 10:40:36 AM
|
INSP-Sprinkler Rough-in | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | PART |
Rick Jackson
|
|
|
forest ###-#### area 7 and 8 first floor okay; area 7 and 8 second floor require earthquake on 4 inch south side and at 2 hour wall east side. will verify the spacing in soffit in area 8 7/25/2001 3:44:39 PM
|
INSP-Supply line flush | 6/28/2001 | 6/28/2001 | 6/28/2001 | P | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/28/2001 3:22:31 PM underground flush only okay
|
FIR-Aging Inspection | 6/19/2001 | 6/19/2001 | 6/19/2001 | | NR |
Rick Jackson
|
|
|
work still under progress 6/19/2001 10:37:20 AM
|
Issue and Print Permit | | | 3/20/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 3/1/2001 | 3/1/2001 | 3/1/2001 | | DONE |
|
|
|
|
Telephone call | | | 3/1/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/20/2001 | | 3/1/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 1/10/2001 | | 3/1/2001 | | DONE |
|
|
|
3/1/2001 15:51:07 JWA - activity updated through activity FIRA22 from case FIR01-00011.
|
Telephone call | | | 1/24/2001 | | DONE |
Bill Alexander
|
|
|
Called Shawn Fenneran of failed review and asked for meeting due to large list of problems (also associated with FIR01-00010).
|
Sprinkler Plan Check | 1/10/2001 | | 1/24/2001 | | FAIL |
Bill Alexander
|
|
|
Fire Code problems with design spacing, etc.
|
Application received | | | 1/10/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|