INSP-Final Inspection | 12/28/2001 | 12/28/2001 | 12/28/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 12/28/2001 9:42:30 AM
|
DOC - Permit Finaled | 12/28/2001 | 12/28/2001 | 12/28/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 12/28/2001 9:45:35 AM
|
INSP-Alarm Testing | 12/21/2001 | 12/21/2001 | 12/21/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/21/2001 4:32:44 AM preaction system not working; c/n issued for ther items 12/24/2001 5:54:14 AM
|
INSP-Alarm Testing | 12/20/2001 | 12/20/2001 | 12/20/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/20/2001 6:20:07 AM need to complete basement alarm testing 12/21/2001 4:33:16 AM
|
INSP-Alarm Testing | 12/19/2001 | 12/19/2001 | 12/19/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/19/2001 11:36:36 AM not finished testing 12/20/2001 6:20:49 AM
|
INSP-Alarm Testing | 12/17/2001 | 12/18/2001 | 12/18/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/17/2001 4:48:55 PM some horns not working; identified on plans; not complete with the install 12/19/2001 11:37:18 AM
|
INSP-Alarm Testing | 12/17/2001 | 12/17/2001 | 12/17/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/17/2001 at 10:03:55. Contact: ###-####. wlak through of second and third floor for horn/strobe locations: items marked on approve plans, will continue on 12/18 12/17/2001 5:00:09 PM
|
INSP-Alarm Testing | 12/7/2001 | 12/7/2001 | 12/7/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/7/2001 5:58:53 AM completed first floor alarms; c/n issued 12/7/2001 3:28:52 PM
|
INSP-Alarm Testing | 12/5/2001 | 12/6/2001 | 12/6/2001 | P | FAIL |
Rick Jackson
|
|
|
###-#### david started testing the first floor; sprinklers not monitored; strobes in corridors over 15 ft from ends; detectors at door hold opens in wronglocation 12/7/2001 6:01:04 AM
|
Override - Parcel Holds | | | 12/5/2001 | | DONE |
Annett Moore
|
|
|
Parcel Tag Notes: Prior to issuance of a final occupancy permit the parking structure to the east shall be completed. Per Tempra K. Wilson X3836. Reason for OverRide: fire alarm inspect
|
FIR-Aging Inspection | 10/15/2001 | 10/15/2001 | 10/15/2001 | | NR |
Rick Jackson
|
|
|
wip 10/15/2001 7:27:35 AM
|
Inspection Record Card- Fire | 7/16/2001 | | 7/16/2001 | | DONE |
|
|
|
|
Telephone call | | | 7/16/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 7/16/2001 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/13/2001 | | PASS |
|
|
|
Two complete sets of revised plans re-submitted today. Comments revised to reflect additional drawings included in this re-submittal.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/13/2001 | | PASS |
|
|
|
|
Alarm Plan Check | | | 6/28/2001 | | PASS |
|
|
|
Resubmittal revisions acceptable. Incompete set of plans submitted (only initiating circuit sheets re-submitted), cannot return stamped plans. Called vendor for complete set to stamp.
|
Plan assigned to (SAM) | 1/19/2001 | | 4/27/2001 | | DONE |
|
|
|
4/27/2001 08:00:07 JWA - activity updated through activity FIRA22 from case FIR01-00264.
|
Alarm Plan Check | | | 2/2/2001 | | PEND |
|
|
|
Conditional approval given to begin work, with additional resubmittal info required to follow for permit issuance.
|
Application received | | | 1/19/2001 | | |
|
|
|
|