INSP-Final Inspection | 8/22/2001 | 8/22/2001 | 8/22/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 8/22/2001 4:07:08 PM
|
DOC - Permit Finaled | 8/22/2001 | 8/22/2001 | 8/22/2001 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/22/2001 4:08:15 PM
|
INSP-Final Inspection | 8/16/2001 | 8/17/2001 | 8/17/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/16/2001 at 13:17:16. Contact: ###-####. c/n issued 8/17/2001 4:31:16 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2001 | 8/1/2001 | 8/1/2001 | P | PART |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 8/1/2001 1:47:52 PM hydro on overhead okay. 8/1/2001 2:57:30 PM
|
INSP-Supply line flush | 7/26/2001 | 7/30/2001 | 7/30/2001 | A | PASS |
Rick Jackson
|
|
|
underground flush Mick ###-####
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/9/2001 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/9/2001 | | 5/9/2001 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/9/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/8/2001 | | DONE |
|
|
|
called left message telling them they need to call me so we can find out what is going on.
|
Sprinkler Plan Check | 5/3/2001 | | 5/7/2001 | | PASS |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 4/6/2001 | | 4/26/2001 | | FAIL |
Bill Alexander
|
|
|
Lack correct design area in rack storage area. Plans and calculations do not match, etc. etc.
|
Telephone call | | | 4/26/2001 | | DONE |
|
|
|
Faxed copy of failed review 5:30pm to Grinnell.
|
Plan assigned to (Bill) | 2/7/2001 | | 3/8/2001 | | DONE |
|
|
|
3/8/2001 13:23:26 JWA - activity updated through activity FIRA22 from case FIR01-00107.
|
Sprinkler Plan Check | 2/8/2001 | | 2/21/2001 | | FAIL |
Bill Alexander
|
|
|
Lack to much detail and correlating information to make a plan review complete.
|
Miscellaneous action | | | 2/21/2001 | | DONE |
|
|
|
Sent all (6) but one set to the front desk for calling and returning.
|
Telephone call | | | 2/21/2001 | | DONE |
|
|
|
Faxed copy of failed review and notification to Grinnell.
|
Telephone call | | | 2/21/2001 | | DONE |
|
|
|
called left message
|
Application received | | | 2/7/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|