Permit Information
Permit NumberFIR01-00050
StatusFinaled
Name GRINNELL FIRE PROTECTION
Site Address 380 E PARKCENTER BLVD
Project NameALM-PARKCENTER PLACE
Customer Number 
ePlanReviewNo
Description
Parkcenter place - To replace an existing fire alarm panel and all connected smoke detectors. The system is required for offsite fire sprinkler monitoring, and also includes complete manual pulls, elevator recall, and voluntary smoke detection in selected areas.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/4/20023/4/20023/4/2002APASS
DetailsRick Jackson
Added by Inspector: 409 On 3/4/2002 10:51:22 AM
INSP-Sprinkler Rough-in/Hydro3/4/20023/4/20023/4/2002ACANC
DetailsRick Jackson
Scheduled by Inspector: 409 On 3/4/2002 10:51:49 AM
DOC - Permit Finaled3/4/20023/4/20023/4/2002APASS
DetailsRick Jackson
Finaled by inspector at 3/4/2002 10:54:46 AM
INSP-Final Inspection2/25/20022/28/20022/28/2002AFAIL
DetailsRick Jackson
###-#### need to locate inspectors test for flow switch; retest flow switch; need ceiling tiles in several areas; need record of completion; sign on door of riser room 2/28/2002 9:06:15 AM
INSP-Alarm Testing2/21/20022/25/20022/25/2002PNR
DetailsRick Jackson
###-#### galem will reshedule 2/25/2002 4:47:54 PM
INSP-Final Inspection9/14/20019/18/20019/18/2001AFAIL
DetailsRick Jackson
deliah-- ###-#### c/n issued; stopped test when elevator recall didn't work 9/18/2001 4:04:59 PM
FIR-Aging Inspection7/18/20017/18/20017/18/2001 NR
DetailsRick Jackson
work in progress 7/18/2001 11:21:09 AM
Issue permit  4/18/2001 DONE
Inspection Record Card- Fire4/12/2001 4/12/2001 DONE
Telephone call  4/12/2001 DONE
called permit ready
PLANS/APPL TAKEN TO FRONT DESK  4/10/2001 PASS
4/6 plan approved but 2nd set for field copy not submitted. HOLD for additional plan set to be submitted.
An additional $100 applies for 3rd submittal.
Alarm Plan Check  4/6/2001 PASS
Approved with Conditions. 3rd submittal.
Plan assigned to (SAM)2/12/2001 4/6/2001 DONE
4/6/2001 18:30:30 SLR - activity updated through activity FIRA22 from case FIR01-00050.
Alarm Plan Check  3/23/2001 FAIL
Resubmittal still inadequate. Faxed revised comments to vendor and discussed by phone.
Application received  2/12/2001  
Alarm Plan Check2/16/2001   FAIL
faxed comments to vendor.