Permit Information
Permit NumberFIR01-00093
StatusFinaled
Name SIMPLEX
Site Address 316 W WASHINGTON ST
Project NameALM-ST LUKES IS CENTER
Customer Number 
ePlanReviewNo
Description
ST LUKES IS Center - To install a new fire alarm system, to provide required sprinkler and HVAC monitoring plus smoke detection in hallways and above and below the floor of the computer room, heat detection in basement, full building manual pull stations with complete a/v annunciation. Work is part of TI remodel.NOTE: The building permit is to change occupancy use from "I1.1" (NURSING HOME) to "B" (OFFICE). To remodel the 19,480 sq.ft. main floor for office's & support services space for "SLRMC Information Services", serving the internal functions of St. Luke's R.M.C. The 1,440 s.f. basement is for service of the building only (mechanical/electrical). Work to include selective demolition of interior walls; removal of portion of existing roof structure to raise the roof elevation w/ new structure, above the new computer room; construction of interior walls to form offices, accessibility upgrades throughout; to upgrade exterior walls at North & East to 1-hour construction w/ protected openings / penetrations & rated parapets; new exterior wall finish; install new "Class C" roof covering system, drainage and parapet screen on South & West walls, with new RTU HVAC equipment & support structure; and interior refurbishment of ceiling, wall & floor finishes w/ electrical, plumbing, mechanical & sprinkler /alarm systems upgrades.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled8/23/20018/23/20018/23/2001APASS
DetailsRick Jackson
Finaled by inspector at 8/23/2001 9:12:21 AM
INSP-Final Inspection8/23/20018/23/20018/23/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 8/23/2001 9:11:53 AM
Alarm Plan Check  8/9/2001 PASS
Approved plan modifications to add releasing and monitoring of the computer room Pre-action sprinkler system to the new FAC panel. Smoke detectors for such were included in originally approved plans. Revised Review comments issued.
PLANS/APPL TAKEN TO FRONT DESK  8/9/2001 PASS
Approved plan modifications to add releasing and monitoring of the computer room Pre-action sprinkler system to the new FAC panel. Smoke detectors for such were included in originally approved plans. Revised Review comments issued.
A $100 fee applies for this modification, due to this being the 3rd plan submittal.
Inspection Record Card- Fire8/9/2001 8/9/2001 DONE
CHANGE STATUS TO (ISS)  8/9/2001 DONE
INSP-Final Inspection7/16/20017/18/20017/18/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/16/2001 at 10:35:10. Contact: ###-####. c/n issued 7/18/2001 4:05:20 PM
INSP-Final Inspection7/12/20017/13/20017/13/2001ACANC
DetailsRick Jackson
###-####
Miscellaneous action  6/25/2001 PASS
Approved changing computer room underfloor ion-type smoke detectors to photoelectric type for better relability. Memo approved and issued directly to vendor and Fire Inspector. No fee applies.
Issue and Print Permit  6/5/2001 DONE
Alarm Plan Check  5/30/2001 PASS
Resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  5/30/2001 PASS
Inspection Record Card- Fire5/30/2001 5/30/2001 DONE
Telephone call  5/30/2001 DONE
Alarm Plan Check  3/14/2001 FAIL
comments faxed to vendor
Plan assigned to (SAM)3/1/2001 3/9/2001 DONE
3/9/2001 16:43:46 JWA - activity updated through activity FIRA22 from case FIR01-00079.
Application received  3/1/2001