DOC - Permit Finaled | 2/1/2002 | 2/1/2002 | 2/1/2002 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 2/1/2002 3:22:54 PM Fire sprinkler system finaled
|
INSP-Final Inspection | 1/24/2002 | 1/24/2002 | 1/24/2002 | P | FAIL |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 1/24/2002 7:45:28 PM provide spare heads in head box with wrench, provide caps and chains on hose valves, provide sprinkler canopies at the top of the south stairs, provide flexible coupling on 3" riser in penthouse, replace clappers in backflow preventer, verify that the 2nd, 3rd and 4th floors flow switches meet the 90 second rule, verify sprinkler at the top of the north shaft, install heat collector at the bottom of the north shaft above head, time main flow switch, send supervisory and trouble signals from the main riser room
|
INSP-Sprinkler Rough-in/Hydro | 1/9/2002 | 1/9/2002 | 1/9/2002 | P | PART |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 1/9/2002 2:13:57 PM Basement, 1st, 2nd, 3rd and 4th floor sprinkler rough-in OK. Riser room, stand pipes, floor control valving, elevator shafts and finished lobby areas have not been reviewed
|
INSP-Sprinkler Rough-in | 7/31/2001 | 8/1/2001 | 8/1/2001 | A | PART |
Joe Tawney
|
|
|
###-#### OK on spklr rough in exc for 3rd flr link which has not been constructed 8/1/2001 10:07:25 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/31/2001 | 7/31/2001 | 7/31/2001 | P | PART |
Joe Tawney
|
|
|
###-#### Ok on hydro test exc for 3rd flr link which has not been constructed 8/1/2001 10:06:28 AM
|
INSP-Supply line flush | 5/2/2001 | 5/3/2001 | 5/3/2001 | A | PART |
Joe Tawney
|
|
|
. 5/3/2001 11:44:38 AM OK on underground hydro test and OK on supply line flush 5/3/2001 11:45:14 AM
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2001 | 3/29/2001 | 3/29/2001 | P | NR |
Joe Tawney
|
|
|
Sam ###-#### Not ready to be rescheduled 3/30/2001 8:50:05 AM
|
INSP-Sprinkler Rough-in/Hydro | 3/27/2001 | 3/28/2001 | 3/28/2001 | A | CANC |
Joe Tawney
|
|
|
###-####--cancel per sam
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2001 | 3/28/2001 | 3/28/2001 | P | NR |
Joe Tawney
|
|
|
Not ready to be rescheduled 3/29/2001 8:06:16 AM
|
INSP-Sprinkler Rough-in | 3/21/2001 | 3/22/2001 | 3/22/2001 | A | PART |
Joe Tawney
|
|
|
OK to cover suppl line 3/22/2001 12:52:56 PM
|
Issue permit | | | 3/13/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | 3/12/2001 | | 3/12/2001 | | DONE |
|
|
|
|
Telephone call | | | 3/12/2001 | | DONE |
|
|
|
CALLED PERMIT READY AND FEES DUE
|
Plan assigned to (Bill) | 3/7/2001 | | 3/12/2001 | | DONE |
|
|
|
3/12/2001 14:41:19 JWA - activity updated through activity FIRA22 from case FIR01-00098.
|
Sprinkler Plan Check | 3/8/2001 | | 3/12/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/12/2001 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 3/7/2001 | | PASS |
Bill Alexander
|
|
|
|