INSP-Final Inspection | 1/6/2004 | 1/6/2004 | 1/6/2004 | P | PASS |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 1/6/2004 at 6:14:28 AM. Contact: ###-####.
|
DOC - Permit Finaled | 1/6/2004 | 1/6/2004 | 1/6/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 1/6/2004 4:24:24 PM
|
INSP-Final Inspection | 12/23/2003 | 12/23/2003 | 12/23/2003 | P | FAIL |
Troy Cobbley
|
|
|
The Ames backflow preventor is having a surging problem which won't allow the flow switch to activate. Owner needs to provide verification that the building will be provided with minimum heating for the wet sprinkler system 12/23/2003 4:28:17 PM
|
INSP-Supply line flush | 12/17/2003 | 12/17/2003 | 12/17/2003 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro test is ok 12/18/2003 8:36:37 AM
|
INSP-Sprinkler Rough-in | 11/25/2003 | 11/26/2003 | 11/26/2003 | A | FAIL |
Troy Cobbley
|
|
|
dave ###-#### Final inspection needs to be done which is to include signs on riser, head box with heads and wrench, knox box, inspection tag for riser, site glass, test bell, lock control valves in open position and anything else the review notes may have. The original installing contractor that started the project is now out of business 11/26/2003 3:17:21 PM
|
INSP-Conference | 10/21/2003 | 10/21/2003 | 10/21/2003 | P | DONE |
Troy Cobbley
|
|
|
secure insulation in the southeast corner of the attic area, remove sheet rock in roof access stairway or provide one additional upright sprinkler in combustible space, provide sprinkler upright at the top of the elevator shaft, mount signs, provide head box, lock control valves in the open position, provide knox key box, provide tag per review note 36, test alarm bell and flow system
|
INSP-Supply line flush | 11/20/2002 | 11/21/2002 | 11/21/2002 | A | PASS |
Troy Cobbley
|
|
|
supply line flush is ok. The main city line appears to be full of rust. 11/21/2002 10:25:22 AM
|
INSP-Final Inspection | 11/20/2002 | 11/21/2002 | 11/21/2002 | P | NR |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 11/20/2002 at 11:55:17. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 6/18/2002 | 6/19/2002 | 6/19/2002 | A | PART |
Troy Cobbley
|
|
|
OK to cover on the upper floor. other items on the correction list need to be completed 6/19/2002 9:55:33 AM
|
INSP-Sprinkler Rough-in/Hydro | 6/13/2002 | 6/13/2002 | 6/13/2002 | P | PART |
Troy Cobbley
|
|
|
above ground hydro test OK. Some items on the correction list completed 6/13/2002 3:52:15 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2002 | 6/12/2002 | 6/12/2002 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 06/12/2002 at 10:31:23. Contact: ###-####.
|
INSP-Sprinkler Rough-in | 5/23/2002 | 5/24/2002 | 5/24/2002 | A | FAIL |
Troy Cobbley
|
|
|
Hydro test failed, provide additional hanger on 3" main in south west corner of basement, provide sprinkler head in elevator shaft (per plan), provide retaining straps on all top beam clamps in basement, additional sprinkler heads may be required in spaces and the top and bottom of the east stairs, secure insulation to deck, provide earthquake bracing were all thread rod exceeds 6" in length, resubmitt plans that show the feed main changes to the second floor system 5/24/2002 10:47:56 AM
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2002 | 5/22/2002 | 5/22/2002 | A | FAIL |
Troy Cobbley
|
|
|
Piping would not hold water-hydro failed 5/22/2002 3:29:57 PM
|
INSP-Supply line flush | 3/23/2001 | 3/26/2001 | 3/26/2001 | A | FAIL |
Joe Tawney
|
|
|
Supply line cover Fail Add washers at outside wall 3/26/2001 1:08:52 PM
|
INSP-Supply line flush | 3/26/2001 | 3/26/2001 | 3/26/2001 | P | PART |
Joe Tawney
|
|
|
ok TO COVER SUPPLY LINE 3/27/2001 8:21:53 AM
|
INSP-Supply line flush | 3/26/2001 | 3/26/2001 | 3/26/2001 | P | PART |
Joe Tawney
|
|
|
ok TO COVER SUPPLY LINE 3/27/2001 8:21:53 AM
|
Issue and Print Permit | | | 3/23/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/22/2001 | | 3/22/2001 | | DONE |
|
|
|
|
Telephone call | | | 3/22/2001 | | DONE |
|
|
|
called clarence gave dollar amount
|
Plan assigned to (Bill) | 3/15/2001 | | 3/19/2001 | | DONE |
|
|
|
3/19/2001 10:41:06 JWA - activity updated through activity FIRA22 from case FIR01-00124.
|
Sprinkler Plan Check | 3/15/2001 | | 3/19/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2001 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 3/15/2001 | | PASS |
Bill Alexander
|
|
|
|