Permit Information
Permit NumberFIR01-00126
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1835 W COMMERCE AVE
Project NameSPR TRIMCO
Customer Number 
ePlanReview 
Description
* TRIMCO * Installing U.G. & O.H. fire sprinkler system to meet current high piled and rack storage warehouse requirements of 1997 UFC. This facility has 2 separate dry systems (which exceed volume limitation and are required to meet the 60 second water flow response time). (Reference installers letter on record of required conformance). Underground piping is 8" C-900 (type is not shown on the drawing), with ductile iron entering the building to the base of riser. Both systems are designed for .30/2600-ft/2 w/high temperature heads (required) with 96 ft/2 maximum spacing per head spacing. Offices are designed for Light Hazard. No building permit attached with this permit. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/200312/8/200312/8/2003APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/5/2003 at 4:30:50 PM. Contact: ###-####.
DOC - Permit Finaled12/8/200312/8/200312/8/2003APASS
DetailsRick Jackson
Finaled by inspector at 12/8/2003 8:17:44 AM
INSP-Final Inspection10/27/200310/29/200310/29/2003PPASS
DetailsRick Jackson
all deficencies remedied. Please call 1 hour prior to arrival; Phone #: ###-#### Internet Inspection Request from: Trent Bice will close out sthis permit when alarms (FIR01-00152) is completed; still need test certificates 10/29/2003 3:40:00 PM
INSP-Sprinkler Rough-in/Hydro8/14/20038/15/20038/15/2003AFAIL
DetailsRick Jackson
Trip tests, and alarm test on the fire sprinkler system. Please call in the A.M. so we can have things ready when you arrive.; Phone #: ###-#### Internet Inspection Request from: Trent Bice need head under overhead door and return bends; remove main; need sign on door - Fire Sprinkler Controls - Fire Alarm Panel; keep hose valves clear of storage; obtain approval for 62 second trip time; provide locks on EOL acclerator; lock on PIV; PIV tamper undergorund conduit not listed for underground service; 8/15/2003 11:48:10 AM
(F) Reprint permit  7/29/2003 DONE
Issue and Print Permit  7/29/2003 DONE
Sprinkler Plan Check7/22/2003 7/28/2003 PASS
DetailsBill Alexander
Revised system #2 piping to drop volume for required trip time test.
PLANS/APPL TAKEN TO FRONT DESK  7/28/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire7/28/2003 7/28/2003 DONE
Telephone call  7/28/2003 DONE
permit ready and fees due
Plan resubmittals received  7/22/2003  
DetailsBill Alexander
Miscellaneous action  6/3/2003 DONE
DetailsBill Alexander
Sent email to S. Fenneren to get this project going and finished.
Telephone call  5/13/2003 DONE
DetailsBill Alexander
Contractor called and said the (new) FM approved DPV was shipped from Israel. Questioned me if their hold up on sprinklers would hold up a BLD. My answer was "no", not if they show continuing work to get it finaled.
INSP-Conference4/15/20034/15/20034/15/2003PDONE
DetailsRick Jackson
Talked to Trent (Shilo) and told him he has 30 days to complete the work; he said they have delays in communication with the maker of the new valve; he is due back in town next Wednesday and will provide info on the valve to Bill Alexander; I asked about the trip times and he said that at 21 psi it takes 1:08 and at 17 psi it takes 57 seconds
INSP-Sprinkler Rough-in/Hydro4/26/20024/29/20024/29/2002PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/26/2002 at 16:31:42. Contact: ###-####. reviewed c/n issued - some items corrected; storage height of records too high; need to verify EQ's in west warehouse; 4/29/2002 4:49:39 PM
INSP-Sprinkler Rough-in/Hydro11/2/200111/2/200111/2/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/02/2001 at 08:21:12. Contact: ###-####. c/n issued; too long to list 11/2/2001 4:24:47 PM
Issue permit  11/1/2001 DONE
Telephone call  10/31/2001 DONE
permit ready
PLANS/APPL TAKEN TO FRONT DESK  10/31/2001 DONE
DetailsBill Alexander
Sprinkler Plan Check10/25/2001 10/31/2001 PASS
DetailsBill Alexander
Requires fire hose resubmittal meeting requirements of NFPA 13:5-15.5, and UFC 8102.9.
INSP-Sprinkler Rough-in/Hydro10/23/200110/24/200110/24/2001ANR
DetailsRick Jackson
Scheduled by Inspector: 409 On 10/23/2001 4:39:21 PM need plans at job; told Trent that I need the plans before inspection 10/25/2001 7:23:28 AM
INSP-Sprinkler Rough-in/Hydro10/22/200110/23/200110/23/2001PNR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/22/2001 at 09:37:56. Contact: ###-####.
Sprinkler Plan Check7/17/2001 7/19/2001 FAIL
DetailsBill Alexander
Resubmittal on Firematic Exhauster - to meet NFPA 13:4-2.3.1 (volume limitations) . Does not meet listing requirements of manufacturers use and application, required per NFPA 13:3-1.1.
INSP-Supply line flush6/1/20016/4/20016/4/2001PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 06/01/2001 at 13:29:05. Contact: ###-####. underground flush okay 6/4/2001 2:07:00 PM
INSP-Supply line flush5/31/20016/1/20016/1/2001ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/31/2001 at 15:00:26. Contact: ###-####. United Water will turn on valve on Monday 6/4/01 6/1/2001 10:23:05 AM
INSP-Supply line flush5/24/20015/24/20015/24/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/24/2001 at 08:27:21. Contact: ###-####. underground installed is 8 inch per plans but PIV not installed. Shilo notified per telephone call to Pepper 5/24/2001 11:37:29 AM
Issue and Print Permit  4/6/2001 DONE
Inspection Record Card- Fire4/4/2001 4/4/2001 DONE
Telephone call  4/4/2001 DONE
LEFT MESS THAT PERMIT IS READY
Plan assigned to (Bill)3/15/2001 4/2/2001 DONE
4/2/2001 14:04:15 SLR - activity updated through activity FIRA22 from case FIR01-00126.
Sprinkler Plan Check3/28/2001 4/2/2001 PASS
Re-submittal. Consider only as 2 submittals. Revisions made by RLD
PLANS/APPL TAKEN TO FRONT DESK  4/2/2001 DONE
Sprinkler Plan Check3/15/2001 3/19/2001 FAIL
DetailsBill Alexander
LACK NFPA MINIMUM REQUIREMENTS.
Telephone call  3/19/2001 DONE
DetailsBill Alexander
FAXED COPY OF FAILED REVIEW NOTES
Application received  3/15/2001 PASS
DetailsBill Alexander
Case Summary    DONE
Case Summary    DONE