DOC - Permit Finaled | 12/17/2001 | 12/17/2001 | 12/17/2001 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 12/17/2001 10:32:00 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/13/2001 | 7/13/2001 | 7/13/2001 | P | PART |
Joe Tawney
|
|
|
OK on above ground hydro test except FDC piping 7/13/2001 2:39:32 PM
|
INSP-Sprinkler Rough-in | 7/2/2001 | 7/3/2001 | 7/3/2001 | A | PART |
Joe Tawney
|
|
|
Spklr rough in Finish EQ bracing at risers, Add 1 head in storage area, Address beam obstruction in storage area 7/2/2001 4:58:11 PM
|
Sprinkler Plan Check | 5/1/2001 | | 5/3/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2001 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/3/2001 | | 5/3/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/3/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 5/3/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/2/2001 | | DONE |
|
|
|
High piled storage areas lack design information? Hose stations lacking? Questions on 3 different water supply data information from United Water?
|
Sprinkler Plan Check | | | 4/23/2001 | | FAIL |
|
|
|
faxed review comments to contractor.
|
Application received | | | 4/3/2001 | | FAIL |
Bill Alexander
|
|
|
Lacked complete fire sprinkler design cover sheets.
|
Plan assigned to (Bill) | 4/3/2001 | | 4/3/2001 | | DONE |
|
|
|
4/3/2001 20:52:15 SLR - activity updated through activity FIRA22 from case FIR01-00149.
|
Case Summary | | | | | DONE |
|
|
|
|