INSP-Final Inspection | 6/27/2001 | 6/29/2001 | 6/29/2001 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/27/2001 at 10:55:54. Contact: ###-####.
|
DOC - Permit Finaled | 6/29/2001 | 6/29/2001 | 6/29/2001 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/29/2001 10:35:00 AM
|
INSP-Sprinkler Rough-in/Hydro | 6/6/2001 | 6/6/2001 | 6/6/2001 | P | PASS |
Rick Jackson
|
|
|
Don ###-#### pager hydro okay; alarms/tampers not complete; need calc stickers, blue tag, aux drain sign 6/6/2001 3:52:20 PM
|
Issue and Print Permit | | | 5/30/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/22/2001 | | 5/29/2001 | | PASS |
Bill Alexander
|
|
|
Revised Remote area calculations with rack sprinkler modifications.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/29/2001 | | DONE |
Bill Alexander
|
|
|
3rd review / changes in remote area #3 commodity and racking change.
|
Inspection Record Card- Fire | 5/29/2001 | | 5/29/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/29/2001 | | DONE |
|
|
|
called permit ready
|
INSP-Sprinkler Rough-in | 5/24/2001 | 5/24/2001 | 5/24/2001 | P | PART |
Rick Jackson
|
|
|
###-#### pager okay to cover the lunch room. upper mezzanine and assembly room only 5/25/2001 5:58:53 AM
|
Issue permit | | | 5/4/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 4/9/2001 | | 5/3/2001 | | DONE |
|
|
|
5/1/2001 20:50:08 SLR - activity updated through activity FIRA22 from case FIR01-00269.
|
Sprinkler Plan Check | 5/1/2001 | | 5/3/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2001 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/3/2001 | | 5/3/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/3/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 4/30/2001 | | 5/1/2001 | | FAIL |
Bill Alexander
|
|
|
Head missing in Test area #5. System design does not match NFPA 13: (Lack more detail to intent of design for some some areas1. Commodities, design hazard, system design intent.
|
Telephone call | | | 5/1/2001 | | DONE |
|
|
|
Faxed failed review 5:10pm
|
Sprinkler Plan Check | 4/10/2001 | | 4/26/2001 | | FAIL |
Bill Alexander
|
|
|
Lack sufficient sprinkler data design information for rack storage areas.
|
Telephone call | | | 4/26/2001 | | DONE |
Bill Alexander
|
|
|
Called Jeff Anderson/TV Fire and asked for more design information on rack storage design.
|
Application received | | | 4/9/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|