DOC - Permit Finaled | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/9/2001 3:31:41 PM
|
INSP-Final Inspection | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/9/2001 6:33:22 PM Fire alarm system finaled. OK for perm occ.
|
DOC - Permit Finaled | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/9/2001 6:33:32 PM
|
INSP-Final Inspection | 11/7/2001 | 11/8/2001 | 11/8/2001 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler system finaled. OK for perm occ 11/9/2001 3:31:20 PM
|
Telephone call | | | 11/6/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 11/6/2001 | | |
|
|
|
|
Sprinkler Plan Check | 11/5/2001 | | 11/5/2001 | | PASS |
Bill Alexander
|
|
|
Revised calculations and piping changes for the use of stroage to 20'-0" in Denver Matress. Change out roof sprinklers in Sofa Mart warehouse for storage to 20'-0" and 4'-6" to 5'-0" aisle spacing. Requires asbuilt drawing and data prior to acceptance/final
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/5/2001 | | DONE |
Bill Alexander
|
|
|
|
INSP-Final Inspection | 11/1/2001 | 11/2/2001 | 11/2/2001 | P | FAIL |
Troy Cobbley
|
|
|
Contractor did not have approvals on new rack storage heights and east antifreeze loop failed hydro 11/2/2001 4:47:26 PM
|
INSP-Sprinkler Rough-in | 10/18/2001 | 10/18/2001 | 10/18/2001 | P | PART |
Troy Cobbley
|
|
|
left c/n. Oak express max stor. is 15'. Top shelf is now at 15'. no storage allowed on top shelf. EQ bracing is con. to bottom and mid chord. prove it will work or move to top chord. 10/18/2001 11:21:52 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2001 | 10/16/2001 | 10/16/2001 | P | PART |
Troy Cobbley
|
|
|
Hydro on Sofa mart, denver mattress and overhead supply line OK. Rough-in on sofa mart and denver mattress OK but see c/n, 10/16/2001 12:48:43 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/28/2001 | 10/5/2001 | 10/5/2001 | A | CANC |
Joe Tawney
|
|
|
###-#### MIKE
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2001 | 10/4/2001 | 10/4/2001 | P | PART |
Joe Tawney
|
|
|
Oak Express hydro OK. Fire pump test OK 10/4/2001 5:36:45 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2001 | 10/4/2001 | 10/4/2001 | P | CANC |
Joe Tawney
|
|
|
Cancel double entry 10/3/2001 8:13:07 AM
|
Inspection Record Card- Fire | 9/21/2001 | | 9/21/2001 | | DONE |
|
|
|
|
Telephone call | | | 9/21/2001 | | DONE |
|
|
|
|
Issue permit | | | 9/21/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/20/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 9/10/2001 | | 9/20/2001 | | PASS |
Bill Alexander
|
|
|
|
INSP-Final Inspection | 9/17/2001 | 9/18/2001 | 9/18/2001 | P | PART |
Joe Tawney
|
|
|
OK on supply line flush and Ok on underground hydro test 9/18/2001 4:04:27 PM
|
Telephone call | | | 9/13/2001 | | DONE |
Bill Alexander
|
|
|
Called Steven Scandaliato (designer) to verify separations, letter of commodity storage limitations for Denver Mattress, required head data submittals, etc.
|
Telephone call | | | 8/31/2001 | | DONE |
|
|
|
Received a phone (9:00 am) call from Susan @ 800 ###-#### (rack people for Denver Mattress). Want infomartion on what they are wanting to install. The sprinkler design did not cover the type they want to install and that info should go back to Owner/Architect to trickle back to the Sprinkler Contractor.
|
Sprinkler Plan Check | 8/9/2001 | | 8/20/2001 | | FAIL |
Bill Alexander
|
|
|
Resumittal of changes and new addtion. Changes on UG not approved without letter. New addtion and racking thoughout need reverified with correct and correlating information (plans & calcs).
|
Telephone call | | | 8/20/2001 | | DONE |
|
|
|
Faxed copy of 2nd submittal FAILED review. 7:30am
|
Telephone call | | | 8/20/2001 | | DONE |
|
|
|
called and talked to Troy told him he will need to come and pick up permit as per bill alexander.mps 8/20/01
|
Miscellaneous action | | | 8/17/2001 | | DONE |
|
|
|
Fax copy of resubmittal (failed) review. Put hold on anymore inspections on project.
|
INSP-Supply line flush | 8/15/2001 | 8/16/2001 | 8/16/2001 | A | PART |
Joe Tawney
|
|
|
OK to cover supply line 8/16/2001 11:18:00 AM
|
Sprinkler Plan Check | 8/9/2001 | | 8/15/2001 | | FAIL |
Bill Alexander
|
|
|
Underground has changed locations with no explanation which requires OH supply main from north to south inside this facility.
|
INSP-Sprinkler Rough-in | 7/11/2001 | 7/11/2001 | 7/11/2001 | P | PART |
Joe Tawney
|
|
|
OK to cover small rooms in SE corner of bldg 7/11/2001 3:48:43 PM
|
Issue permit | | | 6/15/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/13/2001 | | 6/13/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/9/2001 | | 6/13/2001 | | DONE |
|
|
|
6/13/2001 13:58:24 JWA - activity updated through activity FIRA22 from case FIR01-00314.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/13/2001 | | DONE |
Bill Alexander
|
|
|
This is the first review for standard system coverage
|
Sprinkler Plan Check | 6/6/2001 | | 6/12/2001 | | PASS |
Bill Alexander
|
|
|
Approved on conditions (reference attached notes)
|
Sprinkler Plan Check | 5/9/2001 | | 5/11/2001 | | FAIL |
Bill Alexander
|
|
|
Lacked sufficient information to verify system. (UFC 1001.3)
|
Telephone call | | | 5/11/2001 | | DONE |
Bill Alexander
|
|
|
Called for meeting to explain failed plan. To extensive for letter.
|
Miscellaneous action | | | 5/11/2001 | | DONE |
Bill Alexander
|
|
|
Mailed letter requested meeting.
|
Telephone call | | | 5/11/2001 | | DONE |
Bill Alexander
|
|
|
Faxed letter requested meeting.
|
Application received | | | 5/9/2001 | | FAIL |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|