FIR-Aging Inspection | 12/10/2002 | 12/10/2002 | 12/10/2002 | | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 12/10/2002 | 12/10/2002 | 12/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/10/2002 1:03:31 PM
|
Issue and Print Permit | | | 2/5/2002 | | DONE |
|
|
|
|
Telephone call | | | 9/24/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/12/2001 | | 7/12/2001 | | DONE |
|
|
|
|
Telephone call | | | 7/12/2001 | | DONE |
|
|
|
called Mike Basey and left a message that permit is ready for pickup
|
Plan assigned to (SAM) | 5/11/2001 | | 7/12/2001 | | DONE |
|
|
|
7/12/2001 09:35:59 SLR - activity updated through activity FIRA22 from case FIR01-00320.
|
Alarm Plan Check | 6/7/2001 | | 7/12/2001 | | HOLD |
|
|
|
6/7/01 - revised bulidng plans submitted showing a different exiting system from the Banquet rooms than approved by the Building Plan reviewer. Modifications referred to the Bldg Inspector for a decision of acceptablility.
7/12/01 - Per site visit by Carl and George, the new exiting system will be acceptable with field modifications to the opening hardware. This will provide direct exit to the outside form the banquet room. Duct detectors therefore not required int hte 2 HVAC ahu's serving the Baquet room. Still awating revised fire alarm plans to be resubmitted per 5/29/01 review.
|
Alarm Plan Check | | | 7/12/2001 | | PASS |
|
|
|
Per 7/11 telcon/agreement with Protex, to expedite this project, revised FA plans will not be required. Original submitted plans will be approved with CONDITIONS of necessary modifications to be satisfactorily field verified by the Fire Inspector for final acceptance.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/12/2001 | | PASS |
|
|
|
|
Alarm Plan Check | | | 5/29/2001 | | FAIL |
|
|
|
Review comments faxed to submitter and to Protex, based on submitted plans, the meeting of 5/18/01 and a letter dated 5/18/01 received 5/24/01 from Musgrove Engineering.
|
Telephone call | | | 5/23/2001 | | DONE |
|
|
|
telcon with David Asmus, regarding his 5/18/01 letter indicating direct access exits are provided from the Banquet room. These are not direct per the plans approved by our Bldg dept. If field modifications have been made, these will have to be documented, and re-submitted for approval by the Bldg Dept.
|
Meeting | | | 5/18/2001 | | |
|
|
|
Meeting with Rob Ahten, Peter Schadt, and contractor re FA plan revisions required. To submit additional information on two HVAC units which aren't shown to have duct detectors for shut down, justifying no detection or adding detection if necessary. Also need plans showing connection of Ansul system to FAC panel and revise plans to show D1-122 to be for a HP unit shut down, not for smoke damper release. Other work is acceptable as shown on plans and approval was granted to begin installation of those new devices as shown.
|
Application received | | | 5/11/2001 | | |
|
|
|
|