Permit Information
Permit NumberFIR01-00326
StatusFinaled
Name TREASURE VALLEY FIRE
Site Address 11550 W PRESIDENT DR
Project NameSPR BENTE BUILDING
Customer Number 
ePlanReview 
Description
BENTE BUILDING - TO INSTALL AN ORDINARY GROUP II HAZARD SYSTEM IN A NEW 23,430 SQUARE FOOT, ONE STORY, CONCRETE TILT-UP SHELL & CORE BUILDING AND RELATED SITE IMPROVEMENTS. THIS BUILDING WILL BE FULLY FIRE SPRINKLERED. THIS BUILDING WILL INCLUDE THREE FUTURE TENANT SPACES. TENANT SPACE #1 AND #2 ARE TO HAVE A VANILLA FINISH WITH FINISHED RESTROOMS. TENANTS SPACE #1 IS 2,000 FT/2, TENANT SPACE #2 IS 3870 FT/2. THE THIRD TENANT SPACE IS TO BE COMPLETED FOR OCCUPANCY FOR SPECIALTY PLASTICS AND FABRICATION, INC., UNDER BLD01-00309. THIS WORK IS ATTACHED TO BLD01-00290. UNDERGROUND FIRE LINE WAS INSTALLED UNDER FIR01-00279. ALL FIRE SPRINKLER WORK PER NFPA 13, UFC, BCO, THE APPROVED PLANS AND ATTACHED COMMENT LIST, AS REGULATED BY THE FIRE DEPARTMENT.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/14/200111/14/200111/14/2001PPASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/14/2001 12:50:04 PM Fire sprinkler system finaled
DOC - Permit Finaled11/14/200111/14/200111/14/2001PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/14/2001 12:50:22 PM
INSP-Final Inspection10/10/200110/11/200110/11/2001APART
DetailsTroy Cobbley
Aboveground and underground hydro test OK 10/10/2001 3:03:42 PM 10/10/2001 3:04:03 PM
INSP-Sprinkler Rough-in10/5/200110/8/200110/8/2001APASS
DetailsJoe Tawney
Rough-in OK
INSP-Sprinkler Rough-in10/4/200110/5/200110/5/2001ACANC
DetailsJoe Tawney
###-#### mike r/i to be rescheduled 10/5/2001 2:25:36 PM
INSP-Supply line flush9/20/20019/20/20019/20/2001PPART
DetailsJoe Tawney
Added by Inspector: 406 On 9/20/2001 12:01:03 PM OK on supply line flush
FIR-Aging Inspection9/6/20019/6/20019/6/2001 NR
DetailsJoe Tawney
WIP 9/6/2001 11:59:29 AM
Issue and Print Permit  6/7/2001 DONE
PLANS/APPL TAKEN TO FRONT DESK  6/6/2001 DONE
DetailsBill Alexander
Inspection Record Card- Fire6/6/2001 6/6/2001 DONE
Telephone call  6/6/2001 DONE
talked to joe to verify plans are ready
Sprinkler Plan Check5/31/2001 6/5/2001 PASS
DetailsBill Alexander
Need several submittals to provided and attached to plans for clarification and verification of equipment and engineering. (See review notes).
Plan assigned to (Bill)5/18/2001 6/4/2001 DONE
6/4/2001 13:49:31 SLR - activity updated through activity FIRA22 from case FIR01-00329.
Sprinkler Plan Check5/18/2001 5/29/2001 FAIL
DetailsBill Alexander
To many questions to not warrant an approval. Calculated heads @ 9'-0" with a reduction allowance @ 19'-0" (4lb loss with heads @ the roof) for QR's? Plastics tree not identified for hazard design, i.e. Table 7-3.3.1.1 and 7-3.3.2.2? Area/Density design is 130 ft/2 yet no head is spaced (verifying pipe friction loss for 130 ft/2 spacing) on this system.
Telephone call  5/29/2001 DONE
DetailsBill Alexander
Contacted Jeff Anderson and provided questions. Faxed copy of failed items to Tressure Valley Fire.
Application received  5/18/2001 PASS
DetailsBill Alexander
Case Summary    DONE