INSP-Final Inspection | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/14/2001 12:50:04 PM Fire sprinkler system finaled
|
DOC - Permit Finaled | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/14/2001 12:50:22 PM
|
INSP-Final Inspection | 10/10/2001 | 10/11/2001 | 10/11/2001 | A | PART |
Troy Cobbley
|
|
|
Aboveground and underground hydro test OK 10/10/2001 3:03:42 PM 10/10/2001 3:04:03 PM
|
INSP-Sprinkler Rough-in | 10/5/2001 | 10/8/2001 | 10/8/2001 | A | PASS |
Joe Tawney
|
|
|
Rough-in OK
|
INSP-Sprinkler Rough-in | 10/4/2001 | 10/5/2001 | 10/5/2001 | A | CANC |
Joe Tawney
|
|
|
###-#### mike r/i to be rescheduled 10/5/2001 2:25:36 PM
|
INSP-Supply line flush | 9/20/2001 | 9/20/2001 | 9/20/2001 | P | PART |
Joe Tawney
|
|
|
Added by Inspector: 406 On 9/20/2001 12:01:03 PM OK on supply line flush
|
FIR-Aging Inspection | 9/6/2001 | 9/6/2001 | 9/6/2001 | | NR |
Joe Tawney
|
|
|
WIP 9/6/2001 11:59:29 AM
|
Issue and Print Permit | | | 6/7/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/6/2001 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 6/6/2001 | | 6/6/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/6/2001 | | DONE |
|
|
|
talked to joe to verify plans are ready
|
Sprinkler Plan Check | 5/31/2001 | | 6/5/2001 | | PASS |
Bill Alexander
|
|
|
Need several submittals to provided and attached to plans for clarification and verification of equipment and engineering. (See review notes).
|
Plan assigned to (Bill) | 5/18/2001 | | 6/4/2001 | | DONE |
|
|
|
6/4/2001 13:49:31 SLR - activity updated through activity FIRA22 from case FIR01-00329.
|
Sprinkler Plan Check | 5/18/2001 | | 5/29/2001 | | FAIL |
Bill Alexander
|
|
|
To many questions to not warrant an approval. Calculated heads @ 9'-0" with a reduction allowance @ 19'-0" (4lb loss with heads @ the roof) for QR's? Plastics tree not identified for hazard design, i.e. Table 7-3.3.1.1 and 7-3.3.2.2? Area/Density design is 130 ft/2 yet no head is spaced (verifying pipe friction loss for 130 ft/2 spacing) on this system.
|
Telephone call | | | 5/29/2001 | | DONE |
Bill Alexander
|
|
|
Contacted Jeff Anderson and provided questions. Faxed copy of failed items to Tressure Valley Fire.
|
Application received | | | 5/18/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|