Description
SEARS WAREHOUSE & SERVICE CENTER - to upgrade an existing fire alarm system by: replacing existing valve tamper switches, manual pull stations, interior alarm horns, adding four duct detectors for HVAC air handler shut down, a battery charger and verifying/providing a 60-battery supply for the FAC panel.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/26/20036/27/20036/27/2003APASS
DetailsTroy Cobbley
KEVIN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
DOC - Permit Finaled6/27/20036/27/20036/27/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/27/2003 3:02:28 PM
INSP-Conference5/2/20035/2/20035/2/2003APART
DetailsRick Jackson
met with Kevin while performing an inspection for the racking permit (BLD02-02472); the racking was signed by me as all the items were corrected (door hardware/flue space/storage height); I searched the database and found this permit for the alarm system as Steve Keuter had called previously about this permit; I told Keven to get ADT to call for a final inspection as the last inspection was back in 2002 by Troy; he said he would contact ADT to schedule the inspection
INSP-Final Inspection10/18/200210/22/200210/22/2002PFAIL
DetailsTroy Cobbley
batteries in the aux. power supply are not supervized. Provide map at the FACP 10/22/2002 2:50:34 PM
INSP-Final Inspection12/12/200112/13/200112/13/2001PFAIL
DetailsTroy Cobbley
provide additional D113 module for battery supervision and test batteries, adjust tamper switch on gate valve to give steady signal, provide tamper switch on alarm valve trim, adjust flow switch so alarm comes in under 90 seconds, provide map of system at fire alarm panel, provide NFPA 72 forms 12/13/2001 12:38:35 PM
FIR-Aging Inspection10/29/200110/29/200110/29/2001 NH
DetailsTroy Cobbley
Visited job site system is in. I notified contractor that inspection is needed. 10/29/2001 4:04:50 PM
Issue and Print Permit  7/27/2001 DONE
Plan assigned to (SAM)5/22/2001 7/26/2001 DONE
7/26/2001 14:06:43 SLR - activity updated through activity FIRA22 from case FIR01-00330.
Alarm Plan Check  7/26/2001 PASS
2nd Resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  7/26/2001 PASS
Additional $100 fee applies for 3rd review
Inspection Record Card- Fire7/26/2001 7/26/2001 DONE
Telephone call  7/26/2001 DONE
Alarm Plan Check7/2/2001 7/16/2001 FAIL
Resubmittal still inadequate on two items. Review comments faxed to ADT.
Alarm Plan Check  6/6/2001 FAIL
comments faxed to submitter/vendor, ADT.
Application received  5/22/2001