INSP-Final Inspection | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/13/2001 4:08:33 PM OK for perm occ
|
DOC - Permit Finaled | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/13/2001 4:09:31 PM
|
Issue permit | | | 9/13/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/12/2001 | | 9/12/2001 | | DONE |
|
|
|
|
Telephone call | | | 9/12/2001 | | DONE |
|
|
|
called gave dollar amount
|
Sprinkler Plan Check | 8/29/2001 | | 9/11/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/11/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 8/9/2001 | | 8/14/2001 | | FAIL |
Bill Alexander
|
|
|
Does not meet NFPA 13 installation requirements. Other previous issues not addressed or imporperly addressed.
|
Sprinkler Plan Check | 7/9/2001 | | 7/12/2001 | | FAIL |
Bill Alexander
|
|
|
Wrong use of listed heads. Piping run through elevator room. Verify ELO SW piping w/calcs. Riser room seperation missing/outside system control required.
|
Plan assigned to (Bill) | 5/23/2001 | | 6/20/2001 | | DONE |
|
|
|
6/20/2001 08:02:40 JWA - activity updated through activity FIRA22 from case FIR01-00300.
|
Sprinkler Plan Check | 5/23/2001 | | 5/31/2001 | | FAIL |
Bill Alexander
|
|
|
Does not meet NFPA requirements for coverage, listing application, etc.
|
Telephone call | | | 5/31/2001 | | DONE |
Bill Alexander
|
|
|
faxed copy of review to Shilo-Shawn Fenneran.
|
Application received | | | 5/23/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|