Permit Information
Permit NumberFIR01-00336
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 222 S AUTO DR
Project NameSPR LARRY H. MILLER AUTO
Customer Number 
ePlanReview 
Description
LARRY H. MILLER SUNDANCE DODGE AUTO FACILITY EXPANSION -TO FIRE SPRINKLER A NEW 51,245 FT/2, TWO STORY, AUTO SALES AND SERVICE FACILITY (EXPANSION) ON THE SOUTH SIDE OF THE EXISTING FACILITY. THIS EXPANSION WORK INCLUDES A SHOW ROOM AND AUTO PARTS AND SERVICE AREAS. THE STRUCTURE WILL CONSIST OF MASONRY EXTERIOR WALLS, STEEL STRUCTURAL FRAME AND METAL ROOF SYSTEM. THIS EXPANSION IS BEING SEPARATED FROM THE EXISTING BUILDING BY A NEW FOUR-HOUR FIRE-RESISTIVE MASONRY AREA SEPARATION WALL. THIS BUILDING REQUIRES FULL FIRE SPRINKLER PROTECTION TO BE USED FOR ALLOWABLE AREA INCREASE. THE UNDERGROUND FIRE LINE SUPPLY PERMIT IS: FIR01-00300, TAKEN OUT BY THE SAME CONTRACTOR. ALL FIRE SPRINKLER WORK SHALL BE PER THE APPROVED PLANS AND ATTACHED COMMENT LIST, MEETING THE UFC AND BCO, INSTALLED PER RELATED AND ADOPTED NFPA STANDARDS, AS REGULATED BY THE FIRE DEPARTMENT. THIS PERMIT IS A PHASE I PROJECT. (PHASE II IS TO DEMOLISH A PORTION OF THE EXISTING BUILDING AND REMODEL THE REMAINING PORTION). THIS PERMIT DOES NOT INCLUDE THE APPROVAL OF ANY WORK INCLUDED IN PHASE II, WHICH WILL REQUIRE A SEPARATE PERMIT. THIS WORK PERMIT IS ATTACHED TO: BLD00-03944. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/200111/13/200111/13/2001PPASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/13/2001 4:08:33 PM OK for perm occ
DOC - Permit Finaled11/13/200111/13/200111/13/2001PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/13/2001 4:09:31 PM
Issue permit  9/13/2001 DONE
Inspection Record Card- Fire9/12/2001 9/12/2001 DONE
Telephone call  9/12/2001 DONE
called gave dollar amount
Sprinkler Plan Check8/29/2001 9/11/2001 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  9/11/2001 DONE
DetailsBill Alexander
Sprinkler Plan Check8/9/2001 8/14/2001 FAIL
DetailsBill Alexander
Does not meet NFPA 13 installation requirements. Other previous issues not addressed or imporperly addressed.
Sprinkler Plan Check7/9/2001 7/12/2001 FAIL
DetailsBill Alexander
Wrong use of listed heads. Piping run through elevator room. Verify ELO SW piping w/calcs. Riser room seperation missing/outside system control required.
Plan assigned to (Bill)5/23/2001 6/20/2001 DONE
6/20/2001 08:02:40 JWA - activity updated through activity FIRA22 from case FIR01-00300.
Sprinkler Plan Check5/23/2001 5/31/2001 FAIL
DetailsBill Alexander
Does not meet NFPA requirements for coverage, listing application, etc.
Telephone call  5/31/2001 DONE
DetailsBill Alexander
faxed copy of review to Shilo-Shawn Fenneran.
Application received  5/23/2001 PASS
DetailsBill Alexander
Case Summary    DONE