DOC - Permit Finaled | | | 7/31/2001 | | PASS |
Joe Tawney
|
|
|
Finaled for Joe Tawney per response (email) 07/31/01.
|
INSP-Sprinkler Rough-in/Hydro | 7/25/2001 | 7/26/2001 | 7/26/2001 | A | PASS |
Joe Tawney
|
|
|
OK on spklr rough in and OK on above ground hydro test 7/26/2001 2:40:30 PM
|
INSP-Final Inspection | 7/25/2001 | 7/26/2001 | 7/26/2001 | A | PASS |
Joe Tawney
|
|
|
Final Pass OK for certificate of completion 7/26/2001 2:39:52 PM
|
INSP-Supply line flush | 7/25/2001 | 7/26/2001 | 7/25/2001 | A | CANC |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 07/25/2001 at 14:53:50. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 07/25/2001 at 14:54:43.
|
INSP-Sprinkler Rough-in/Hydro | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | PART |
Joe Tawney
|
|
|
OK on spklr rough in add earthquake bracing and change two hangers 7/25/2001 2:17:08 PM
|
INSP-Final Inspection | 7/24/2001 | 7/25/2001 | 7/25/2001 | P | NR |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 07/24/2001 at 13:59:18. Contact: ###-####.
|
INSP-Supply line flush | 7/20/2001 | 7/23/2001 | 7/23/2001 | A | PASS |
Joe Tawney
|
|
|
OK on supply line hydro test 7/23/2001 5:30:07 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2001 | 7/20/2001 | 7/20/2001 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/20/2001 at 10:06:20. Contact: ###-####. will reschedule for 7/23 7/20/2001 3:57:42 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/18/2001 | 7/19/2001 | 7/19/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/18/2001 at 15:17:40. Contact: ###-####. underground hydro failed. leak at riser. 7/19/2001 11:11:28 AM
|
INSP-Supply line flush | 7/17/2001 | 7/17/2001 | 7/17/2001 | P | PART |
Joe Tawney
|
|
|
OK on supply line flush 7/17/2001 10:36:47 AM
|
INSP-Supply line flush | 7/16/2001 | 7/16/2001 | 7/16/2001 | P | CANC |
Joe Tawney
|
|
|
Cancel Water not turned on 7/16/2001 1:27:30 PM
|
INSP-Supply line flush | 7/10/2001 | 7/10/2001 | 7/10/2001 | P | PART |
Joe Tawney
|
|
|
OK to cover spklr supply line 7/10/2001 1:33:44 PM
|
Issue and Print Permit | | | 6/19/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/15/2001 | | 6/15/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/15/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/29/2001 | | 6/15/2001 | | DONE |
|
|
|
6/15/2001 08:08:05 JWA - activity updated through activity FIRA22 from case FIR01-00340.
|
Sprinkler Plan Check | 6/6/2001 | | 6/15/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/15/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 5/29/2001 | | 6/4/2001 | | FAIL |
Bill Alexander
|
|
|
Calc error, using the wrong temp heads, no info on riser room, no info shown of FDC access, data lacking on BFP, compressor, DPV, air maintenance device, need EQ loads, riser incomplete in detail, etc.
|
Application received | | | 5/29/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|