Permit NumberFIR01-00348
StatusExpired
Name GRINNELL FIRE PROTECTION
Site Address 3511 S TK AVE
Project NameSPR BIG O TIRES-COLUMNS
Customer Number 
ePlanReview 
Description
*BIG "O" TIRE* To modifiy/relocate 48 existing (required) column sprinklers on the adjacent side of the same columns to prevent possible damage. NFPA 13:7-9.8.2 COLUMNS WITHIN RUBBER TIRE STORAGE - Where fireproofing is not provided, steel columns shall be protected as follows:
(1) Storage exceeding 15 ft through 20 ft in height — one sidewall sprinkler directed to one side of the column at a 15-ft level.
(2) Storage exceeding 20 ft in height — two sidewall sprinklers, one at the top of the column and the other at a 15-ft level, both directed to the side of the column. All work per NFPA 13 and UFC requirements as regulated by the Fire Department. Permit is not attached to any existing permit. No plans or notes attached. (This is the notes) *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  2/14/2014 DONE
INSP-Conference7/24/20017/24/20017/24/2001PPASS
DetailsRick Jackson
###-#### storage not over 20 ft; heads installed at 15 ft level on 48 columns 7/24/2001 3:41:26 PM
Sprinkler Plan Check6/6/2001 6/6/2001 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/6/2001 DONE
DetailsBill Alexander
Inspection Record Card- Fire6/6/2001 6/6/2001 DONE
Telephone call  6/6/2001 DONE
Issue permit  6/6/2001 DONE
Application received  6/5/2001 PASS
DetailsBill Alexander
Case Summary    DONE