Permit Information
Permit NumberFIR01-00369
StatusFinaled
Name GRINNELL FIRE PROTECTION
Site Address 7699 W SPECTRUM ST
Project NameSPR UG HILTON GRDN INN-BLDG A
Customer Number 
ePlanReview 
Description
HILTON GARDEN INN* To install approximately 210 ft. of 8" C-900 PVC from the (United Water) supply, at the property line, on Spectrum, up to the West Portion of this structure. Underground shall be approved carbon ferrous iron entering the fire sprinkler room with 2" clearance. Also from the fire sprinkler room shall be 2 separate FDC and Dry Standpipe lines, pipe to an accessible location for fire apparatus hook-up. Dry Standpipe shall be 6" C-900 PVC and FDC shall be 4" C-900 PVC to the base of the supply connections. These are 4" and 6" galvanized (inside and out) schedule 40, transitioned at the 90 degree fitting below. Approved accessible ball drips shall be installed on both lines with an auxiliary drain tap installed if the ball drips are solid sealed seats. All rods, nuts, etc. shall be applied with approved coating. Flush and hydro-test per NFPA 13-1999 & 24-1995. Depth shall be minimum 4"-6". All work, materials and installation shall be per UFC, BCO, related and adopted NFPA pamphlets, as regulated per the Fire Department. This permit is attached to BLD01-00729 (West Building structure). Installer must be licenced through the State Fire Marshal's Office. *JWA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20026/18/20026/18/2002PPASS
DetailsTroy Cobbley
Underground system finaled
DOC - Permit Finaled6/18/20026/18/20026/18/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/18/2002 4:23:27 PM
INSP-Sprinkler Rough-in/Hydro4/25/20024/26/20024/26/2002APASS
DetailsTroy Cobbley
3" and 6" risers hydro test OK 4/26/2002 2:52:55 PM
INSP-Sprinkler Rough-in/Hydro4/25/20024/25/20024/25/2002PCANC
DetailsRick Jackson
INSPECTION CANCELD UNTILL 4-26-02///DLD
Override - Parcel Holds  4/25/2002 DONE
DetailsDarla L Downs
Parcel Tag Notes: PLAN MODIFICATION ( BLD01-00729) No inspection for rear of meeting rooms. Elevation change to include roof lantern. May cancel parcel tag when Plan Modification is issued. If any questions please contact Mike Phillips. KMM Reason for OverRide:
Override - Parcel Holds  4/25/2002 DONE
DetailsDarla L Downs
Parcel Tag Notes: PLAN MODIFICATION ( BLD01-00729) No inspection for rear of meeting rooms. Elevation change to include roof lantern. May cancel parcel tag when Plan Modification is issued. If any questions please contact Mike Phillips. KMM Reason for OverRide:
Override - Parcel Holds  4/25/2002  
INSP-Sprinkler Rough-in/Hydro4/23/20024/24/20024/24/2002APASS
DetailsTroy Cobbley
2nd and 3rd floor hydro tests OK 4/24/2002 3:59:34 PM
Override - Parcel Holds  4/23/2002 DONE
DetailsAnnett Moore
Parcel Tag Notes: PLAN MODIFICATION ( BLD01-00729) No inspection for rear of meeting rooms. Elevation change to include roof lantern. May cancel parcel tag when Plan Modification is issued. If any questions please contact Mike Phillips. KMM Reason for OverRide:
INSP-Sprinkler Rough-in3/5/20023/6/20023/6/2002APART
DetailsTroy Cobbley
Pendant sprinkler heads in linen shaft OK for cover 3/6/2002 10:08:50 AM
INSP-Sprinkler Rough-in/Hydro2/20/20022/21/20022/21/2002APART
DetailsTroy Cobbley
hydro test and rough-in for the dry stand pipe system OK. Underground still needs to be tested 2/21/2002 11:33:12 AM
INSP-Sprinkler Rough-in2/11/20022/11/20022/11/2002PCANC
DetailsTroy Cobbley
inspection done under FIR01-00396 2/11/2002 3:48:00 PM
INSP-Sprinkler Rough-in/Hydro1/14/20021/16/20021/16/2002APASS
DetailsTroy Cobbley
Underground flush OK 1/16/2002 9:28:39 AM
INSP-Sprinkler Rough-in/Hydro1/15/20021/15/20021/15/2002PPASS
DetailsTroy Cobbley
Added by Inspector: 430 On 1/15/2002 4:07:17 PM Underground hydro test OK
INSP-Sprinkler Rough-in/Hydro12/12/200112/12/200112/12/2001PPART
DetailsTroy Cobbley
Added by Inspector: 430 On 12/12/2001 3:15:37 PM Heads added in canopy connection to main buiding. OK for cover up. Inspection is for front canopy only
INSP-Sprinkler Rough-in12/11/200112/11/200112/11/2001PFAIL
DetailsTroy Cobbley
this inspection was for front canopy only. heads to be added at connection to building 12/11/2001 12:38:58 PM
INSP-Sprinkler Rough-in7/17/20017/18/20017/18/2001PPART
DetailsJoe Tawney
###-#### OK on 3" main to porte cochere 7/18/2001 1:48:52 PM
Sprinkler Plan Check7/12/2001 7/13/2001 PASS
DetailsBill Alexander
Porte Cochere underground plan submitted addtion.
PLANS/APPL TAKEN TO FRONT DESK  7/13/2001 DONE
DetailsBill Alexander
Porte Coshere underground added.
Telephone call  7/13/2001 DONE
left mess that permit is ready no fees per bill a/mls
Telephone call  7/12/2001 DONE
Called 10:00am, and emailed Nick Anderson (National Fire) indicating I need a permit application with this submittal.
INSP-Sprinkler Rough-in6/27/20016/28/20016/28/2001PPART
DetailsJoe Tawney
OK to cover supply line. FDC and Standpipe lines only stubbed 5 ft from riser room.Lines to be run to above ground location later. 6/28/2001 1:59:19 PM
Issue and Print Permit  6/25/2001 DONE
Issue and Print Permit  6/25/2001 DONE
Inspection Record Card- Fire6/20/2001 6/20/2001 DONE
Telephone call  6/20/2001 DONE
left mess that permit is ready
PLANS/APPL TAKEN TO FRONT DESK  6/20/2001 DONE
DetailsBill Alexander
Application received  6/19/2001 PASS
DetailsBill Alexander
Plan assigned to (Bill)6/19/2001 6/19/2001 DONE
6/19/2001 16:22:56 JWA - activity updated through activity FIRA22 from case FIR01-00369.
Sprinkler Plan Check6/19/2001 6/19/2001 PASS
DetailsBill Alexander
Case Summary    DONE