INSP-Final Inspection | 8/12/2002 | 8/12/2002 | 8/12/2002 | A | PASS |
Troy Cobbley
|
|
|
finaled
|
DOC - Permit Finaled | 8/12/2002 | 8/12/2002 | 8/12/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/12/2002 11:48:17 AM
|
INSP-Final Inspection | 8/12/2002 | 8/12/2002 | 8/12/2002 | A | PASS |
Troy Cobbley
|
|
|
finaled
|
DOC - Permit Finaled | 8/12/2002 | 8/12/2002 | 8/12/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/12/2002 11:48:17 AM
|
INSP-Final Inspection | 7/10/2002 | 7/11/2002 | 7/11/2002 | P | CANC |
Troy Cobbley
|
|
|
not all of the work is complete (windows changed out) 7/11/2002 2:57:02 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2002 | 6/18/2002 | 6/18/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide spare sprinkler heads per note 16, provide canopies for pendants, provide additional hangers in conference rooms, provide canopies and ceiling tile in all elevator lobbies, tag risers, provide approval for the window sprinklers and meet requirements 6/18/2002 12:27:11 PM
|
INSP-Final Inspection | 6/18/2002 | 6/18/2002 | 6/18/2002 | P | PART |
Troy Cobbley
|
|
|
fire sprinkler system given temp per Dave Miller for the window sprinklers
|
INSP-Sprinkler Rough-in/Hydro | 6/14/2002 | 6/17/2002 | 6/17/2002 | A | PART |
Troy Cobbley
|
|
|
Hydro test of both FDCs and the 1st floor dry system OK. 6/17/2002 3:46:37 PM
|
Override - Parcel Holds | | | 6/17/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 6/14/2002 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2002 | 3/29/2002 | 3/29/2002 | A | PASS |
Troy Cobbley
|
|
|
4th floor hydro test OK, OK to cover pool area and small south side dry system 3/29/2002 3:04:14 PM
|
Telephone call | | | 3/7/2002 | | DONE |
|
|
|
permit ready
|
Issue permit | | | 3/7/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/5/2002 | | 3/6/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/6/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 2/8/2002 | | 2/20/2002 | | FAIL |
Bill Alexander
|
|
|
Added corridor window sprinkler protection columns N and 14, and modified dry system over conference 109 entry, columns 5 to 7 and north of R, plan sheets FP-2.
Failed due to many questions on installation of window sprinklers.
|
Miscellaneous action | | | 2/20/2002 | | FAIL |
|
|
|
Plan taken to front desk for calling and return of deficient plans.
|
Telephone call | | | 2/20/2002 | | DONE |
|
|
|
called, plans failed, need to pick up and resubmit
|
INSP-Sprinkler Rough-in | 2/11/2002 | 2/11/2002 | 2/11/2002 | P | PART |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 2/11/2002 2:42:54 PM 2nd floor rough-in OK. OK to cover
|
INSP-Sprinkler Rough-in | 1/31/2002 | 2/1/2002 | 2/1/2002 | A | PART |
Troy Cobbley
|
|
|
3rd floor rough-in OK 2/1/2002 8:24:06 AM
|
INSP-Sprinkler Rough-in | 1/31/2002 | 2/1/2002 | 2/1/2002 | P | CANC |
Troy Cobbley
|
|
|
duplicate inspection 1/31/2002 4:25:41 PM
|
FIR-Aging Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | | NR |
Troy Cobbley
|
|
|
work in progress 2/1/2002 11:39:27 AM
|
INSP-Sprinkler Rough-in/Hydro | 1/25/2002 | 1/25/2002 | 1/25/2002 | A | PART |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 1/25/2002 11:07:08 AM Attic dry system rough-in Ok now that difficiencies are corrected. 4th floor wet system rough-in OK. Tenting/boxes over some 4th floor pipe to be inspected later
|
INSP-Sprinkler Rough-in/Hydro | 1/22/2002 | 1/23/2002 | 1/23/2002 | P | FAIL |
Troy Cobbley
|
|
|
Attic dry system hydro failed 1/23/2002 3:33:31 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/23/2002 | 1/23/2002 | 1/23/2002 | P | PART |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 1/23/2002 3:36:00 PM Rough-in OK for the attic system. Contractor to relocate two upright sprinkler heads at east end. Left notice with General Contractor that draft stops and sheer walls need to be installed to separate sprinkler heads that are too close down mechanical corridor
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/27/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 12/19/2001 | | 12/27/2001 | | PASS |
Bill Alexander
|
|
|
Attic system modifications.
|
Issue permit | | | 12/27/2001 | | DONE |
|
|
|
|
Telephone call | | | 12/26/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/3/2001 | | DONE |
|
|
|
|
Issue permit | | | 10/3/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/27/2001 | | 10/3/2001 | | PASS |
Bill Alexander
|
|
|
Final approval on original design.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/3/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 9/24/2001 | | DONE |
|
|
|
reminder call
|
Inspection Record Card- Fire | 7/19/2001 | | 7/19/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/12/2001 | | 7/19/2001 | | PASS |
Bill Alexander
|
|
|
Partial approval only. Need resubmittal verification of misc. items.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/19/2001 | | DONE |
Bill Alexander
|
|
|
For Partial Approval
|
Plan assigned to (Bill) | 7/12/2001 | | 7/13/2001 | | DONE |
|
|
|
7/13/2001 10:40:26 JWA - activity updated through activity FIRA22 from case FIR01-00369.
|
Application received | | | 7/12/2001 | | PASS |
Bill Alexander
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
Called Nick Anderson and went over plan problems (irregularities).
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|