INSP-Final Inspection | 12/17/2002 | 12/18/2002 | 12/18/2002 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 12/18/2002 1:51:53 PM
|
DOC - Permit Finaled | 12/18/2002 | 12/18/2002 | 12/18/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 12/18/2002 1:51:57 PM
|
INSP-Alarm Testing | 12/16/2002 | 12/17/2002 | 12/17/2002 | A | FAIL |
Troy Cobbley
|
|
|
separate the low air signals from the tamper switches signals, provide key and map for the knox box 12/17/2002 2:52:46 PM
|
INSP-Alarm Testing | 12/7/2001 | 12/10/2001 | 12/10/2001 | A | CANC |
Troy Cobbley
|
|
|
duplicate inspection 12/10/2001 4:13:07 PM
|
INSP-Final Inspection | 12/7/2001 | 12/7/2001 | 12/7/2001 | P | FAIL |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 12/7/2001 3:35:45 PM Provide tamper switches on control valves in riser room, provide tamper switch on dry pipe alarm trim, provide "Fire Sprinkler Room" sign on riser room, hard wire the air compressor, provide lock on fire alarm panel circuit, provide "knox box", provide map in knox box and at facp, provide low air pressure switch, verify single pressure switch is ok for two dry pipe risers, test exterior bell and sign
|
Issue and Print Permit | | | 11/27/2001 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/16/2001 | | 11/19/2001 | | DONE |
|
|
|
11/19/2001 08:33:44 SLR - activity updated through activity FIRA22 from case FIR01-00401.
|
Alarm Plan Check | | | 11/16/2001 | | PASS |
|
|
|
Resubmittal approved with CONDITIONS
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/16/2001 | | PASS |
|
|
|
|
Alarm Plan Check | 7/16/2001 | | 7/17/2001 | | FAIL |
|
|
|
Preliminary cursory review; plans inadequate for a FAC panel replancement. Review comments faxed to vendor.
|
Application received | | | 7/16/2001 | | |
|
|
|
|