Telephone call | | | 7/8/2003 | | DONE |
|
|
|
telcon from Earl Lasater, requested copy of the plan review comments; faxed to him at new number ###-####.
|
Telephone call | | | 2/20/2003 | | DONE |
|
|
|
I called Earl Lasater, Fire Sentry regarding status. Fire Sentry designed the system but Intergrated Systems from SLC installed it, ca. june 2002; FS had nothing to do with the installation but was to be involved for the final inspection. I explained the current situation and gave him names and phone numbers at Stock Components: Will Punkoney ###-#### and Chris Zummerschied ###-####. Earl will contact them to see if they want Fire Sentry to represent them to get this permit re-issued and get it finaled, as required for a C of O.
|
INSP-Conference | 2/10/2003 | 2/10/2003 | 2/10/2003 | A | PART |
Rick Jackson
|
|
|
talked to Earl Lassiter of Fire Sentry and he will get with the tenant about getting a final inspection
|
FIR-Aging Inspection | 12/20/2002 | 12/20/2002 | 12/20/2002 | | PART |
Rick Jackson
|
|
|
called Earl of Fire Sentry and he said he is looking into it 12/20/2002 8:24:09 AM
|
Issue permit | | | 12/18/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/3/2001 | | 12/3/2001 | | DONE |
|
|
|
|
Telephone call | | | 12/3/2001 | | DONE |
|
|
|
left mess for earl that permit is ready
|
Alarm Plan Check | 11/29/2001 | | 11/30/2001 | | PASS |
|
|
|
Rush request. 11/29 plans finally acceptable after resubmitting 11/30 revisions.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/30/2001 | | PASS |
|
|
|
|
Plan assigned to (SAM) | 11/14/2001 | | 11/14/2001 | | DONE |
|
|
|
was never issued sam had the plans all along.
|
Alarm Plan Check | | | 11/14/2001 | | FAIL |
|
|
|
Resubmitted plans received 11/5 not acceptable. Revised review faxed to and 11/15-discussed revised review with Earl Lasater, Fire Sentry Systems. System is being designed by a firm in SLC, which has created delays in response. I stressed urgency of getting these plans corrected and installation completed quickly due to notice of FD pending action for the illegal occupancy status of the tenant.
|
Issue and Print Permit | | | 10/29/2001 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/19/2001 | | 10/25/2001 | | DONE |
|
|
|
10/25/2001 14:43:49 JWA - activity updated through activity FIRA22 from case FIR01-00566.
|
Alarm Plan Check | | | 8/2/2001 | | FAIL |
|
|
|
faxed review comments to Fire Sentry.
|
Application received | | | 7/19/2001 | | |
|
|
|
|