INSP-Final Inspection | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/13/2001 4:09:12 PM OK for perm occ
|
DOC - Permit Finaled | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/13/2001 4:09:37 PM
|
INSP-Alarm Testing | 11/8/2001 | 11/9/2001 | 11/9/2001 | A | FAIL |
Troy Cobbley
|
|
|
Provide revised battery calcs, repair water motor gong and provide elevator recall 11/9/2001 4:56:13 PM
|
Inspection Record Card- Fire | 10/11/2001 | | 10/11/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/11/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 10/11/2001 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/10/2001 | | PASS |
|
|
|
final resubmittal received 10/10/01 is acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/10/2001 | | PASS |
|
|
|
A $200.00 resubmittal penalty applies in addition to the normal permit fee.
|
Alarm Plan Check | | | 10/8/2001 | | FAIL |
|
|
|
Still missing approved in-duct detectors for smoke dampers and verification of compatibility of the remote annunciator. Discussed by phone with Rob at Protex, he'll fax necessary info tomorrow.
|
Miscellaneous action | | | 9/20/2001 | | DONE |
|
|
|
resubmittal received
|
Alarm Plan Check | | | 9/7/2001 | | FAIL |
|
|
|
Called Protex to discuss review; not available, left message to call back to discuss review comments. Revised Review faxed to Protex.
|
Alarm Plan Check | | | 8/7/2001 | | FAIL |
|
|
|
Review comments faxed to, and discussed with, vendor, Protex, Rob Ahten. Revised review not faxed, held pending receipt of this additional information.
|
Application received | | | 7/24/2001 | | |
|
|
|
|