Permit Information
Permit NumberFIR01-00410
StatusFinaled
Name JEFF FISHER
Site Address 222 S AUTO DR
Project NameALM-LARRY MILLER SUNDANCE
Customer Number 
ePlanReview 
Description
Larry H. Miller Sundance Dodge - To install a new fire alarm system as part of a building expansion. The new panel will replace the existing FAC panel and will include the new and existing building devices. The system will include offsite monitoring of the fire sprinkler systems, elevator recall functions, in-duct detectors for fire/smoke damper release and duct detectors for HVAC air handler shutdown.
The building permit (BLD00-03194) is: TO CONSTRUCT A NEW 51,245 SQ. FT., TWO STORY, AUTO SALES AND SERVICE FACILITY EXPANSION AT THE SOUTH SIDE OF THE EXISTING SUNDANCE DODGE AUTO FACILITY. THE EXPANSION WILL INCLUDE A SHOW ROOM, AUTO PARTS AND SERVICE AREAS. THE EXPANSION WILL BE CONSTRUCTED OF MASONRY EXTERIOR WALLS, STEEL STRUCTURAL FRAME AND METAL ROOF SYSTEM. THIS EXPANSION IS BEING SEPARATED FROM THE EXISTING BUILDING BY A NEW FOUR-HOUR FIRE-RESISTIVE MASONRY AREA SEPARATION WALL. THIS BUILDING WILL BE FULLY FIRE SPRINKLED. THE SPRINKLERS ARE USED FOR ALLOWABLE AREA INCREASE. THIS PERMIT ALSO INCLUDES RELATED SITE IMPROVEMENTS. ALL CONSTRUCTION PER THE APPROVED PLANS AND ATTACHED COMMENT LIST. THIS PERMIT IS FOR PHASE I OF THIS PROJECT. PHASE II IS TO DEMOLISH A PORTION OF THE EXISTING BUILDING AND REMODEL THE REMAINING PORTION. THIS PERMIT DOES NOT INCLUDE THE APPROVAL OF ANY WORK INCLUDED IN PHASE II. A SEPARATE REVIEW AND PERMIT WILL BE REQUIRED TO DO THE WORK ON PHASE II.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/200111/13/200111/13/2001PPASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/13/2001 4:09:12 PM OK for perm occ
DOC - Permit Finaled11/13/200111/13/200111/13/2001PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/13/2001 4:09:37 PM
INSP-Alarm Testing11/8/200111/9/200111/9/2001AFAIL
DetailsTroy Cobbley
Provide revised battery calcs, repair water motor gong and provide elevator recall 11/9/2001 4:56:13 PM
Inspection Record Card- Fire10/11/2001 10/11/2001 DONE
Telephone call  10/11/2001 DONE
left mess that permit is ready
Issue permit  10/11/2001 DONE
Alarm Plan Check  10/10/2001 PASS
final resubmittal received 10/10/01 is acceptable.
PLANS/APPL TAKEN TO FRONT DESK  10/10/2001 PASS
A $200.00 resubmittal penalty applies in addition to the normal permit fee.
Alarm Plan Check  10/8/2001 FAIL
Still missing approved in-duct detectors for smoke dampers and verification of compatibility of the remote annunciator. Discussed by phone with Rob at Protex, he'll fax necessary info tomorrow.
Miscellaneous action  9/20/2001 DONE
resubmittal received
Alarm Plan Check  9/7/2001 FAIL
Called Protex to discuss review; not available, left message to call back to discuss review comments. Revised Review faxed to Protex.
Alarm Plan Check  8/7/2001 FAIL
Review comments faxed to, and discussed with, vendor, Protex, Rob Ahten. Revised review not faxed, held pending receipt of this additional information.
Application received  7/24/2001